Main menu > Commissioning > Extra configuration > Miscellaneous
Operating line
Time switch
5.1.3

Entering the 24-hour program for space heating

For space heating, a specific 24-hour program can be selected for every day.
Main menu > Time switch
Operating line
Monday through Sunday
Special day
The special day is a 24-hour program which can be activated either via the holiday
program or via an external contact.
Activation of the special day is described in section 5.2 "Holidays/special days".
For each day, a maximum of 6 entries can be made in the 24-hour program.
For an entry, following must be entered:
• Time of day from where the desired operating mode shall apply
• The required operating mode
The next day always adopts the operating mode of the previous day until a specific
entry is made.
Diagram: The operating mode of the previous day is shown as a broken line.
Cmf
PreCmf
Eco
Monday
If no entry is made for a specific day, the operating mode of the previous day will be
adopted for the whole day and shown as a broken line.
The special day starts and ends with the same operating mode.
The day following the special day adopts the operating mode of the previous day's 24-
hour program that would have been valid without the special day.
Cmf
PreCmf
Eco
Monday
When all entries have been made for a day, that 24-hour program can be copied to the
other days. This means that if, for example, Monday has been programmed, that pro-
gram can be copied to all the other working days (Monday through Friday) and need
not be entered again. The program can be copied to Monday through Friday, Monday
through Sunday, or to individual weekdays.
Boiler Sequence Controller RMK770
5 General functions, fundamentals
Range
On / Off
Comfort / Precomfort /
Economy
Comfort / Precomfort /
Economy
1
Tuesday
1
Special day
Remarks
Activation of time
switch
Factory setting
06:00 Comfort
22:00 Economy
06:00 Comfort
22:00 Economy
Wednesday
Wednesday