Faults; Configuration Of The Universal Inputs And Outputs - Siemens Synco700 RMK770 Documentation Handbook

Series modular boiler sequence controller
Table of Contents

Advertisement

Analog inputs
Type
Setting
Measuring range
44/226
Building Technologies
HVAC Products
3.4.7

Faults

Main menu > Commissioning > Extra configuration > Faults > Inputs
Operating line
Fault input 1
Fault input 2
Fault input 3
Fault input 4
Main menu > Commissioning > Extra configuration > Faults > Outputs
Operating line
Fault relay 1
Fault relay 2
For more detailed information, refer to chapter 12 "Function block faults".
3.4.8

Configuration of the universal inputs and outputs

The universal inputs can accept digital signals and passive or active analog signals.
The inputs are activated via the basic and the extra configuration. Together with the
activation, the unit is assigned to the relevant input. For this reason, setting the input
identifier is not required with the RMK770 (with the exception of the 4 universal inputs
for display purposes and the 4 fault inputs).
With the analog inputs, the following settings can be made:
• Type
• Measuring range
• Measured value correction
Temperature sensor Ni 1000 is preselected as standard for all types of temperature
sensors.
The following types of input signals can be handled:
• LG-Ni1000
• 2 × LG-Ni1000
• T1
• Pt1000
• DC 0...10 V
Main menu > Commissioning > Settings > ... or
Main menu > Settings > Inputs > ...X...
Operating line
Type
• Passive temperature signals delivered by LG-Ni 1000 sensing elements have a
measuring range of − 50...− 250 °C
• Passive temperature signals delivered by 2 x LG-Ni 1000 or T1 sensing elements
have a measuring range of − 50...− 150 °C
• Passive temperature signals delivered by Pt1000 sensing elements have a measur-
ing range of − 50...+ 400 °C
• In the case of active signals, the measuring range can be selected. To be entered is
a low and a high limit value.
Boiler Sequence Controller RMK770
3 Commissioning
Range
RMK770..., RMZ7...
RMK770..., RMZ7...
RMK770..., RMZ7...
RMK770..., RMZ7...
Range
RMK770..., RMZ7...*
RMK770..., RMZ7...*
Range
Ni1000 / 2×Ni1000 / T1 /
Pt1000 / 0...10 V
Name
Name
Factory setting
Ni1000
CE1P3132en
01.03.2005