Series modular boiler sequence controller
Table of Contents

Advertisement

Building Technologies
HVAC Products
Number
Text
6001
>1 identical device
address
>1 boiler with ad-
5512
dress number 1
5522
>1 boiler with ad-
dress number 2
>1 boiler with ad-
5532
dress number 3
5542
>1 boiler with ad-
dress number 4
>1 boiler with ad-
5552
dress number 5
5562
>1 boiler with ad-
dress number 6
5591
Failure boiler se-
quence manager
5592
>1 boiler sequence
manager
Boiler Sequence Controller RMK770
13 Communication
Effect
More than 1 device with the same device ad-
dress.
Urgent message; must be acknowledged
2 boilers with boiler address 1.
Nonurgent message; must be acknowledged
2 boilers with boiler address 2
Nonurgent message; must be acknowledged
2 boilers with boiler address 3.
Nonurgent message; must be acknowledged
2 boilers with boiler address 4.
Nonurgent message; must be acknowledged
2 boilers with boiler address 5.
Nonurgent message; must be acknowledged
2 boilers with boiler address 6.
Nonurgent message; must be acknowledged
Nonurgent message; must be acknowledged
Nonurgent message; must be acknowledged
193/226
CE1P3132en
01.03.2005