Settings
Early shutdown max.
Quick setback
Settings
Room temperature
Morning boost
Building Technologies
HVAC Products
omy
or Protection
Precomfort setpoint.
Optimum stop control is only possible if the type of optimization selected is "with room
temperature sensor".
Main menu > Settings > Heating circuit > Optimizations/influences
Operating line
Early shutdown max
Early shutdown max. limits the maximum forward shift. If 00:00 is set, optimum stop
control will be deactivated.

10.8.3 Quick setback and boost heating

The purpose of quick setback is to reach the new setpoint as quickly as possible when
changing the room operating mode.
When quick setback is active, the heating circuit pump is switched off and the heating
circuit mixing valve shut. The heating circuit remains switched off until the required
room temperature is reached.
The "Quick setback" function can be deactivated at the service level.
Main menu > Settings > Heating circuit > Optimizations/influences
Operating line
Quick setback
Quick setback is started when the room operating mode changes from Comfort
Precomfort to Economy or Protection
room temperature has reached the new setpoint or when a change back to Comfort
mode is made.
If a room temperature sensor is connected, the actual value room temperature is used
for aborting quick setback.
If there is no sensor, the temperature of the room model is used to make the calcula-
tion. In that case, the setback time will depend on the outside temperature and the
building time constant.
The purpose of the "Boost heating" function is to have a shorter heating up time.
During boost heating, the room temperature setpoint is raised by an adjustable value.
The room temperature setpoint boost due to the morning boost and the room influence
bring about an increase of the flow temperature setpoint. The larger of the 2 influences
will be active.
Morning boost will be activated when a change is made from Economy mode or Pro-
tection
to Comfort
least 0.25 K below the setpoint.
TR
SpTR
SpCmf
SpEco
TR Room temperature
SP Setpoint
Boiler Sequence Controller RMK770
10 Heating circuit control
mode, the room temperature will lie 0.5 K below the Comfort or
Range
00.00...06:00 h.min
Range
Off / On
. The function will be terminated when the
or Precomfort mode and when the room temperature lies at
TR
SpCmf Setpoint, room operating mode Comfort or Precomfort
SpEco Setpoint, room operating mode Economy or Protection
Factory setting
00:00 h.min
Factory setting
On
SpTR
or
167/226
CE1P3132en
01.03.2005