Communications Mode
7.6.1
Sending Message Frames with the Message Frame Length Specification
You specify the message frame length in bytes with the Send request in word 2.
Note:
The length of the message frame sent by the CPU can vary from the length configured in
parameter block 7 ( 7.3). The length configured in parameter block 7 refers to message frames
received by the CP from a peripheral device.
Procedure for "Send message frames with message frame length specification"
1. The CPU transfers the following in the transfer memory
• The message frame length in bytes in word 2
• The "Coordinate data transfer for sending message frames" job number into word 0.
2. The CPU reads the coordination information from word 0 of the transfer memory.
If the CP has not accepted the job (bit 0 in byte 1= "0"), no message frame can be sent.
The CPU can read the number of message blocks to be sent from byte 6 of the transfer
memory. The number is calculated by the CP using the length specified in the job request. If
you specify a message frame length of 12 bytes, for example, the CP stores the value 02
byte 6 for two message blocks.
3. CP transfers message frame in 8-byte message blocks to the transfer memory.
Note:
The CP stores the number of message frames in the Receive mailbox in byte 7, so you can also
determine after issuing a Send request whether you can receive a message.
7-64
CP 523
in
H