CP 523
The following procedure is recommended:
1. Enter the initialization data in DB 1 using the programmer, and include sufficient commen-
tary.
2. Store DB 1 on floppy or hard disk.
3. Transfer DB 1 to the memory submodule.
Table 7-8.
Entry on the PG 685
:
KS = 'Parameters for the serial';
:
S = 'interface';
:
KS = ':0600100';
:
S = 'Parameters for';
:
KS = '3964(R) mode';
:
S = ':7300100002000040010012003';
7.3.2
Setting the CP 523 Parameters in the User Program
You can transfer data for a parameter block to the CP 523 with a "Transfer parameter setting
data" request (90xx
).
H
Note:
You can only set parameters for parameter blocks 0, 2, 7 and 9 in the user program with
"Transfer parameter setting data". Parameter blocks 1, 3 to 6 and 8 are only significant in Print
mode.
Reader's note: You will find a list of parameters (Tables 7-9 to 7-12) in Section 7.3.2. For editorial
reasons, the parameter blocks are discussed in the order 0, 7, 2, 9.
The parameter tables are followed by the subsections
Setting parameters for TRANSPARENT MODE (page 7-28)
Setting parameters for INTERPRETIVE MODE (page 7-32)
Setting parameters for 3964(R) MODE (page 7-38)
When you have selected the mode you want, you can limit your reading to the
appropriate subsection.
EWA 4NEB 811 6044-02a
Setting Parameter for 3964(R) Mode on the Memory Submodule
Communications Mode
Description
0
Parameter block 0
6
2400 baud
0
Even parity
0
No BUSY signal
1
V.24 (RS232C) interface
0
7 data bits (11-bit frame)
0
Handshaking OFF
:7
Parameter block 7
3
3964(R) mode
00100
Character delay time
D
00200
Time-out
D
00400
Block delay time
D
1
3964R (with BCC)
0
Low priority
012
Connection buildup attempts
D
003
No. of Send attempts
D
7-23