Siemens SIMATIC S5 CP 523 Manual page 126

Serial i/o module
Hide thumbs Also See for SIMATIC S5 CP 523:
Table of Contents

Advertisement

Communications Mode
The following procedure is recommended:
1. Enter the parameter setting data on the programmer in DB 1 and include sufficient comments.
2. Store DB 1 on diskette or hard disk.
3. Transfer DB 1 to the memory submodule.
Table 7-6. Setting the CP 523 Parameters in Interpretive Mode on the Memory Submodule
Entry on the PG 685
:
KS = 'Parameters for the serial';
:
S = 'Interface';
:
KS = ':0600100';
:
S = 'Parameters XON/XOFF';
:
KS = ':2';
:
KH = 1113;
:
S = 'Parameters for ASCII';
:
KS = 'mode';
:
S = ':720030000';
:
KH = 0D0D;
7-20
Explanation
0
Parameter block 0
6
2400 baud
0
Even parity
0
No BUSY signal
1
RS-232-C (V.24) interface
0
7 data bits (11-bit frame)
0
Handshaking OFF
2
Parameter block 2
11
DC1 (XON character)
H
13
DC3 (XOFF character)
H
7
Parameter block 7
2
Interpretive mode
0030
Character delay time 300 ms
D
000
Message frame length 0
D
0D0D
End-of-text characters
H
(two carriage returns)
CP 523
EWA 4NEB 811 6044-02a