Siemens SIMATIC S5 CP 523 Manual page 138

Serial i/o module
Hide thumbs Also See for SIMATIC S5 CP 523:
Table of Contents

Advertisement

CP 523
Example:
Transferring parameter setting data for parameter block 0
Start address 128 is set on the CP 523.
Set CP parameters as follows:
Parameters for the serial interface (parameter block 0)
2400 baud
Even parity
No BUSY system
V.24 (RS 232C) interface
7 data bits (11-bit character frame)
Handshake OFF
STL OB 22
:JU
FB
NAME :SYNC**
:JU
FB
NAME :BLOCK0
:BE
*
5.2
** FB 99 waits until the CP 523 can accept job requests ( 4.1)
Note:
Restart OB 22 is processed only when the CPU is at RUN before switching from "POWER OFF" to
"POWER ON".
Note:
The status byte can be scanned approx. 30 ms after issuing the job request to check on whether
correct parameter values were forwarded (X4 is returned to indicate false values ( 7.4.1)).
EWA 4NEB 811 6044-02a
STL FB 112
99
NAME :BLOCK0
:L
KH 0000
112
:T
PW 134
:L
KH
:T
PW 132
:L
KH
:T
PW 130
:L
KH 9000
:T
PW 128*
:BE
(06
)
H
(00
)
H
(00
)
H
(01
)
H
(00
)
H
(00
)
H
Handshake OFF
7 data bits (11-bit character frame)
No BUSY signal
0001
V.24 (RS 232C) interface
2400 baud
0600
Even parity
Transfer job number for "Parameter
setting data for parameter block 0"
Communications Mode
Explanation
7-33