History Values; Last Trip Data - GE LM10 Instruction Manual

Motor protection system
Table of Contents

Advertisement

CHAPTER 4: FUNCTIONALITY
4.4

History Values

4.4.1

Last Trip Data

LM10 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
Data for the last ten trips is stored in the LM10. Press the HISTORY key to access these
values. Pressing the HISTORY key multiple times scrolls between trips 1 to 10.
GE LM10 1.70
Class: 10
MAC ID: 1
Baud: 500
Last Trip #1
Range:
Overcurrent
Last Trip #1
Range:
Phase A:
0.0
Last Trip #1
Range:
Phase B:
0.0
Last Trip #1
Range:
Phase C:
0.0
Last Trip #1
Range:
GndAmps:
0.0
Last Trip #1
Range:
VOLTs:
220
Last Trip #1
Range:
PowFact: 1.00
Last Trip #1
Range:
KW:
0.0
Last Trip #1
Range:
Avg Cur:
0.0
Last Trip #1
Range:
%CurUnBl:
0
HISTORY VALUES
Overcurrent, Gr. Fault, Jam, Stall,
CuUnbalance, LdLoss, DevNet
Fault, Dev Stop, Voltage, Aux
Sense
0.0 to 3200.0 A
0.0 to 3200.0 A
0.0 to 3200.0 A
0.0 to 25.0 A
0 to 9000 V
0.00 to 1.00
0.0 to 6553.5 kW
0.0 to 3200.0 A
0 to 250%
4–41