Direct Integer Inputs And Outputs - GE N60 Instruction Manual

Network stability and synchrophasor measurement system ur series
Hide thumbs Also See for N60:
Table of Contents

Advertisement

5 SETTINGS
d) APPLICATION EXAMPLE
Direct analog input FlexAnalog parameters (the
in other N60 functions that use FlexAnalog parameters.
The
to
DIR ANA 1 INTEGRITY
to
FORCED
DIR ANA 32 FORCED
operand can be active (logic 1) at any time. If a direct device is offline, all of the associated trigger operands will be inactive
(logic 0).
The following figure illustrates the operation of the direct analogs feature.
In this example, UR-1 is configured to use four out of its 32 analog channels. These four values are selected from two
sources. UR-2 is configured to receive two out of the four analog values sent, and UR-3 is set to receive three values. Note
that
is effectively being received at both UR-2 and UR-3.
SRC 2 FREQ
Pool of
FlexAnalog
parameters
Pool of
FlexAnalog
parameters
Pool of
FlexAnalog
parameters
a) OVERVIEW
PATH: SETTINGS
INPUTS/OUTPUTS
 DIRECT INTEGERS
MESSAGE
GE Multilin
N60 Network Stability and Synchrophasor Measurement System
DIR ANALOG INPUT 1
,
DIR ANA 32 INTEGRITY
DIR ANA 1 DEADBAND
FlexLogic™ operands are provided to indicate the most recent trigger condition: Only one
UR-1
SRC1 P
Analog Out 1
SRC1 PF
Analog Out 2
SRC2 FREQ
Analog Out 3
SRC1 V1 Mag
Analog Out 4
UR-2
Remote Analog 7
Analog In 7
Remote Analog 3
Analog In 3
UR-3
Remote Analog 2
Analog In 2
Remote Analog 3
Analog In 3
Remote Analog 9
Analog In 9
Figure 5–100: DIRECT ANALOGS SAMPLE APPLICATION

DIRECT INTEGERS
 DIRECT INTEGER
 OUTPUTS
 DIRECT INTEGER
 INPUTS
5.8 INPUTS AND OUTPUTS
to
values) are available for use
DIR ANALOG INPUT 32
to
DIR ANA 32 DEADBAND
UR-1 is configured to send four
analog values as outputs 1, 2, 3,
and 4, respectively.
TX
RX
UR-2 is configured to receive
SRC1 P
and
SRC2 FREQ
from
UR-1 as direct analog inputs 7
and 3, respectively.
TX
RX
UR-3 is configured to receive
SRC1 PF SRC2 FREQ
,
, and
SRC1 V1 Mag
from UR-1 as
direct analog inputs 2, 3, and 9,
respectively
847007A1.CDR

5.8.12 DIRECT INTEGER INPUTS AND OUTPUTS

See page 5–238.
See page 5–238.
, and
DIR ANA 1
5
5-237