Advertisement

5 SETTINGS

PATH: SETTINGS
CONTROL ELEMENTS
 FREQUENCY RATE
 OF CHANGE 1
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
Four independent rate of change of frequency elements are available. The element responds to rate of change of fre-
quency with voltage, current and frequency supervision.
FREQ RATE 1 TREND: This setting allows configuring the element to respond to increasing or decreasing frequency,
or to frequency change in either direction.
FREQ RATE 1 PICKUP: This setting specifies an intended
decreasing trend, set
FREQ RATE 1 TREND
condition is:
df dt
Pickup
For applications monitoring an increasing trend, set
old accordingly. The operating condition is:
For applications monitoring rate of change of frequency in any direction set
specify the pickup threshold accordingly. The operating condition is:
FREQ RATE 1 OV SUPV PICKUP: This setting defines minimum voltage level required for operation of the element.
The supervising function responds to the positive-sequence voltage. Overvoltage supervision should be used to pre-
vent operation under specific system conditions such as faults.
FREQ RATE 1 OC SUPV PICKUP: This setting defines minimum current level required for operation of the element.
The supervising function responds to the positive-sequence current. Typical application includes load shedding. Set
the pickup threshold to zero if no overcurrent supervision is required.
GE Multilin
N60 Network Stability and Synchrophasor Measurement System


FREQUENCY RATE OF CHANGE

FREQ RATE 1
FUNCTION: Disabled
FREQ RATE 1 SOURCE:
SRC 1
FREQ RATE 1 TREND:
Increasing
FREQ RATE 1 PICKUP:
0.50 Hz/sec
FREQ RATE 1 OV SUPV
PICKUP: 0.700 pu
FREQ RATE 1 OC SUPV
PICKUP: 0.200 pu
FREQ RATE 1 MIN
FREQUENCY: 45.00 Hz
FREQ RATE 1 MAX
FREQUENCY: 65.00 Hz
FREQ RATE 1 PICKUP
DELAY: 0.000 s
FREQ RATE 1 RESET
DELAY: 0.000 s
FREQ RATE 1 BLOCK:
Off
FREQ RATE 1 TARGET:
Self-Reset
FREQ RATE 1 EVENTS:
Disabled
to "Decreasing" and specify the pickup threshold accordingly. The operating
.
FREQ RATE 1 TREND
df dt
Pickup
5.7 CONTROL ELEMENTS
5.7.11 FREQUENCY RATE OF CHANGE
FREQUENCY RATE OF CHANGE 1(4)
Range: Disabled, Enabled
Range: SRC 1, SRC 2
Range: Increasing, Decreasing, Bi-directional
Range: 0.10 to 15.00 Hz/sec in steps of 0.01
Range: 0.100 to 3.000 pu in steps of 0.001
Range: 0.000 to 30.000 pu in steps of 0.001
Range: 20.00 to 80.00 Hz in steps of 0.01
Range: 20.00 to 80.00 Hz in steps of 0.01
Range: 0 to 65.535 s in steps of 0.001
Range: 0 to 65.535 s in steps of 0.001
Range: FlexLogic operand
Range: Self-Reset, Latched, Disabled
Range: Disabled, Enabled
df dt
pickup threshold. For applications monitoring a
to "Increasing" and specify the pickup thresh-
.
FREQ RATE 1 TREND
abs df dt
Pickup
5
to "Bi-Directional" and
5-209