5 SETTINGS
The settings for the remaining menus are outlined as follows.
PATH: SETTINGS
PRODUCT SETUP
 IEC103 INPUTS
 BINARY
MESSAGE
MESSAGE
 POINT 0
MESSAGE
MESSAGE
 POINT 95
MESSAGE
MESSAGE
The binary input points are mapped using elements from a list of possible FlexLogic operands. A maximum of 96 binary
inputs (points) can be mapped this way.
The IEC60870-5-103 point list always starts with point 0 and ends at the first "Off" value. Since the IEC 60870-5-103 point
list must be in a continuous block, any points assigned after the first "Off" point are ignored.
For each defined point, set appropriate values for the Function Type (FUN) and Information Number (INF), which form the
Information Object Identifier field of the ASDU, as defined in IEC60870-5-103.
The binary input points are sent as Class 1 data. They are sent either as a response to a general interrogation received
from the controller or reported spontaneously. Spontaneous transmission occurs as a response to cyclic Class 2 requests.
If the N60 wants to transmit Class 1 data at that time, it demands access for Class 1 data transmission (ACD=1 in the con-
trol field of the response).
GE Multilin
N60 Network Stability and Synchrophasor Measurement System


COMMUNICATIONS
IEC60870-5-103
 POINT 0
 POINT 1
 POINT 95
POINT 0 FUN
0
POINT 0 INF
0
POINT 0 Input
Off
POINT 95 FUN
0
POINT 95 INF
0
POINT 95 Input
Off
5.2 PRODUCT SETUP
IEC103 INPUTS BINARY
Range: see sub-menu below
Range: see sub-menu below
Range: see sub-menu below
Range: 0 to 255 in steps of 1
Range: 0 to 255 in steps of 1
Range: FlexLogic operand
Range: 0 to 255 in steps of 1
Range: 0 to 255 in steps of 1
Range: FlexLogic operand
5
5-59