B.4 MEMORY MAPPING
Table B–10: MODBUS MEMORY MAP (Sheet 8 of 70)
ADDR
REGISTER NAME
1603
Field Shared Input States
1604
Field Shared Input Channel States
1605
Field Shared Input Test States
1606
Field Shared Output Operand States
1607
Field Latching Output Open Operand States
B
1608
Field Latching Output Close Operand States
1609
Field Latching Output Open Driver States
160A
Field Latching Output Close Driver States
160B
Field Latching Output Physical States
160C
Field Unit Online/Offline States
160D
Field RTD Input Trouble States
160E
Field Transducer Input Trouble States
Ethernet Fibre Channel Status (Read/Write)
1610
Ethernet Primary Fibre Channel Status
1611
Ethernet Secondary Fibre Channel Status
1612
Ethernet Tertiary Fibre Channel Status
Data Logger Actuals (Read Only)
1618
Data Logger Channel Count
1619
Time of Oldest Available Samples
161B
Time of Newest Available Samples
161D
Data Logger Duration
Sensitive Directional Power Actuals (Read Only) (2 Modules)
1680
Sensitive Directional Power 1 Power
1682
Sensitive Directional Power 2 Power
Field Unit RTD Actuals (Read Only) (8 Modules)
16C0
Field RTD x Value
16C1
...Repeated for module number 2
16C2
...Repeated for module number 3
16C3
...Repeated for module number 4
16C4
...Repeated for module number 5
16C5
...Repeated for module number 6
16C6
...Repeated for module number 7
16C7
...Repeated for module number 8
Field Unit Transducer Actuals (Read Only) (8 Modules)
16C8
Field Transducer x Value
16CA
...Repeated for module number 2
16CC
...Repeated for module number 3
16CE
...Repeated for module number 4
16D0
...Repeated for module number 5
16D2
...Repeated for module number 6
16D4
...Repeated for module number 7
16D6
...Repeated for module number 8
Frequency Rate of Change Actuals (Read Only) (4 Modules)
16E0
Frequency Rate of Change 1
16E1
Reserved (3 items)
16E4
...Repeated for Frequency Rate of Change 2
16E8
...Repeated for Frequency Rate of Change 3
16EC
...Repeated for Frequency Rate of Change 4
Source Current (Read Only) (6 Modules)
1800
Source 1 Phase A Current RMS
1802
Source 1 Phase B Current RMS
1804
Source 1 Phase C Current RMS
1806
Source 1 Neutral Current RMS
1808
Source 1 Phase A Current Magnitude
B-16
N60 Network Stability and Synchrophasor Measurement System
RANGE
UNITS
0 to 65535
---
0 to 65535
---
0 to 65535
---
0 to 65535
---
0 to 65535
---
0 to 65535
---
0 to 65535
---
0 to 65535
---
0 to 65535
---
0 to 65535
---
0 to 65535
---
0 to 65535
---
0 to 2
---
0 to 2
---
0 to 2
---
0 to 16
channel
0 to 4294967295
seconds
0 to 4294967295
seconds
0 to 999.9
days
-2147483647 to 2147483647
W
W
-2147483647 to 2147483647
-32768 to 32767
°C
-32.768 to 32.767
---
-327.67 to 327.67
Hz/s
0 to 65535
---
0 to 999999.999
A
0 to 999999.999
A
0 to 999999.999
A
0 to 999999.999
A
0 to 999999.999
A
APPENDIX B
STEP
FORMAT
DEFAULT
1
F500
0
1
F500
0
1
F500
0
1
F500
0
1
F500
0
1
F500
0
1
F500
0
1
F500
0
1
F500
0
1
F500
0
1
F500
0
1
F500
0
1
F134
0 (Fail)
1
F134
0 (Fail)
1
F134
0 (Fail)
1
F001
0
1
F050
0
1
F050
0
0.1
F001
0
1
F060
0
1
F060
0
1
F002
0
0.001
F004
0
0.01
F002
0
1
F001
0
0.001
F060
0
0.001
F060
0
0.001
F060
0
0.001
F060
0
0.001
F060
0
GE Multilin