GE Reason RT430 Technical Manual page 54

Gnss precision-time clock
Hide thumbs Also See for Reason RT430:
Table of Contents

Advertisement

RT430/434
54
RS232
TMARK
DMARK
PPX
Pulse width
Pulse width of 1us
when unlocked
Disable PPS when
unlock time after (s)
Cable delay
compensation
Datagram
On-time-mark
Serial
IRIG-B or DCF77
Polarity: normal or inverted
Signal: OFF, PPS, 100PPS, PPX, PPM, TMARK, DMARK,
IRIG-B, DCF77 or EVENT
Polarity: normal or inverted
Hour: 00 up to 23
Minutes: 00 up to 59
Seconds: 00 up to 59
Year: from 2012 to 2030
Month: January to December
Day: 01 to 31
Hour: 00 up to 23
Minutes: 00 up to 59
Seconds: 00 up to 59
1 pulse-every-2-seconds to 1 pulse-per-day
PPS, PPM, PPX, TMARK and DMARK pulses width from 10
to 990 milliseconds
selected: PPS, PPM, PPX, TMARK and DMARK pulses
width of 1us when unit is unlocked
unselected: pulse width does not change when unit is
unlocked
selected: disable PPS signal when the unit is unlocked
after defined period in seconds
unselected: maintain PPS signal when unit is unlocked
0 up to 999 nanoseconds
Serial datagram
ACEB, NEMEA, GPZDA, Meinberg or Custom
Char: start of first (start of first)
Char: start of last (start of last)
Speed: 38400, 19200, 9600, 4800, 2400 or 1200 bps
Data: 7 or 8
Parity: none, even or odd
Chapter 6 – Configuration