Key Features - GE Reason RT430 Technical Manual

Gnss precision-time clock
Hide thumbs Also See for Reason RT430:
Table of Contents

Advertisement

RT430/434
4

Key Features

14
GNSS clocks - GPS and GLONASS satellite systems as reference;
Mean time accuracy of 50 ns for IRIG-B/PPS signals;
IEEE 1588v2 PTP protocol, with better than 100ns accuracy;
PTP Profile for Power Utility Automation, in accordance with IEC 61850-9-:2016
standard;
PTP Power Profile, in accordance with IEEE C37.238:2011 standard;
NTP/SNTP time server;
PTP and NTP/SNTP simultaneously through each Ethernet port;
High accuracy free-running TCXO internal oscillator, ensuring holdover stability;
Parallel Redundancy Protocol (PRP) in accordance with IEC 62439-3:2016 (only
in RT430);
Status monitoring using SNMP (v1, v2c and v3), including MIB support;
Stationary Mode to keep a locked synchronization even with only one satellite;
Event input to analyze time quality from external events;
Delay compensation for GNSS antenna cables;
Time signals in IRIG-B004, IRIG-B124, or DCF77 format;
Pulses: 100 pulses-per-second, 1 pulse-per-second, 1 pulse-per-minute;
Freely configurable low frequency pulse generator;
Pulse on-time with daily repetition;
User-configurable rules for daylight-saving-time and configurable time zone;
Web Interface for configuring and monitoring, available in five different
languages: English, French, Spanish, Portuguese and Russian
RS232 and RS422/485 serial ports with frequency variable pulse and datagram;
Independent Ethernet network ports 10/100Base-T for configuration and
access to the equipment;
Indicators for monitoring synchronization of GNSS antenna and equipment
status;
19'' Panel Installation;
Full range power supplies;
Redundant power supply.