Network Port And Communication Protocols; Equipment Access; Powering Up; Table 6: Gateway And Dns Server Default Settings - GE Reason RT430 Technical Manual

Gnss precision-time clock
Hide thumbs Also See for Reason RT430:
Table of Contents

Advertisement

RT430/434

Network port and communication protocols

Equipment access

4

Powering Up

36

Table 6: Gateway and DNS Server default settings

Gateway (Ethernet 1)
Server DNS
The Ethernet parameters can be configured through the Web Interface.
To ensure unrestricted access to communication via Ethernet network, the following
ports and protocols should be enabled:
Port
Protocol
80
TCP/IP
123
UDP
161
UDP
319
UDP
320
UDP
443
HTTPS
The Web Interface is designed for configuring and monitoring the unit through a web
browser, if the unit it is accessible from a local network. To use all features through
the Web Interface, make sure to use one of the following web browsers:
Internet Explorer version 7.0 or newer.
Mozilla Firefox version 3.0 or newer.
Google Chrome
Connect to the Web Interface by entering the unit IP address into the address field of
your web browser. After the page is loaded, the unit's Web Interface will open,
allowing the user to operate, monitor, and configure it.
Before energizing the unit, familiarize yourself with all the risks and attention
indicators in the equipment frame.
Connect the power supply (including the ground lead) to the appropriate
terminals.
192.168.0.254
192.168.0.254

Table 7: Gateway and DNS Server

Remote access via Web
NTP/SNTP Time synchronization
SNMP for equipment monitoring
Sending event messages PTP to synchronize
Sending general messages via PTP to synchronize
Establishing a safe connection via Web interface
Chapter 4 – Installation
Description
RT430/434