5.8.2 Setting up the Keeper Function

To set up the Keeper function, follow these steps:
1. Make the Keeper parameters visible by changing parameter 150 (Show Clock Parameters)
to a value of Yes.
2. Make sure that the correct date and time are displayed in
121 (Today's
3. Choose which analog input channel will be used as the input signal to the Keeper. Set up the
analog input channel for the proper analog input configuration. Note that you can also set up
an input from an encoder as the input to the Keeper function.
4. Program
for the Keeper function.
5. Choose the units to be used by the Keeper by changing
desired units. The default is GPM; if you want that unit, you can skip this step. If the option
for units is not available, you can choose to program the engineering units of the drive as the
units of the input function. Do this by selecting User Units for the Keeper Units parameter
and programming
6. Modify
parameter 381 (Keeper Max Scale)
sensor is at its maximum value. For example, if you are using a 4-20 mA sensor and it
produces an output of 0-1000 GPM, then you should configure the analog input to 4-20 mA
and set parameter 381 to a value of 1000. This value should represent the maximum of your
sensor.
7. Verify that the Keeper input signal is scaled correctly. Do this through
(Keeper
Make sure that this value has been scaled correctly.
8. Configure the times that the Keeper will save data. To do this, decide whether you want the
Keeper to save data once, twice, or three times a day. Program this choice into
384 (Keeper Save
Twice a day would be 12 hour; three times a day would be 8 hour.
9. Program the exact time that the Keeper will save data. Do this by programming a time value
into
parameter 382 (Keeper Save
processed variable every 8 or 12 or 24 hours, depending on your selection in Keeper Save
Rate.
10. Now program the rate of the input variable using
selection of this parameter should be made based on the units you are accumulating. For
example, if you are pumping gallons per minute (GPM), program this parameter to minute.
If you are pumping liters per second, program second. The parameter should match the time
base of the units you are accumulating.
11. The Keeper is now set up and ready to collect data. The last step should be to reset the records
to be collected. Depending on the order of parameters programmed, you may have false data
in your initial records. To reset the records, navigate to
and enter a value of 40. This will reset the Keeper records so that valid data can be collected.
The Keeper will collect data until the first save time that you have programmed into the drive.
DPD00089A
Time).
parameter 380 (Keeper Input Cfg)
parameter 805 (Display Units)
Input). This parameter should be displaying the value the sensor is outputting.
Rate). If you want the Keeper to save data once a day, select 24 hour.
Chapter 5: Operation and Programming
parameters 120 (Today's Date)
to the value that is the input signal you chose
parameter 389 (Keeper Units)
to the text you want.
to the value to be displayed with the analog input
Time). The Keeper will save the total value of the
parameter 386 (Keeper Time
parameter 801 (Program Number)
- 56 -
parameter 385
parameter
© 2009 Vacon Incorporated All Rights Reserved
and
to the
Rate). The