Electrical Specifications; Mechanical Specifications - AEMC 3710 User Manual

Clamp-on ground resistance testers
Table of Contents

Advertisement

Electrical Specifications

Measurement Range
Autoranging
1.0 to 1200 Ω
Ground or Leakage Current
Autoranging
1 mA to 30.00 A rms
* Reference conditions: 23°C ± 3K, 50% RH ± 10%, battery at 8 V ± 0.2V,
external magnetic field < 40 A/m, external electrical field < 1 V/m, conductor
centered, loop resistance noninductive. Accuracy % of reading.
Resistance Measurement Frequency: 1689 Hz
Resistance Overload: OL displayed above 1200 Ω
Current Measurement Frequency: 47 to 800 Hz
Current Overload: OL displayed above 30 A rms

MECHANICAL SPECIFICATIONS

Dimensions: 9.25 x 3.94 x 2.17" (235 x 100 x 55 mm)
Weight: 2.2 lbs. (1 kg)
Case Material: Lexan
Ground Resistance Tester Models 3710/3730
Ground Resistance
Range
Resolution
1.0 to 50.0 Ω
50.0 to 100.0 Ω
100 to 200 Ω
200 to 400 Ω
400 to 600 Ω
600 to 1200 Ω
1 to 300 mA
0.300 A to 3.000 A
3.00 A to 30.00 A
®
920A (UL94V2)
Accuracy*
0.1 Ω
± (1.5% + 0.1 Ω)
0.5 Ω
± (2.0% + 0.5 Ω)
1 Ω
± (3.0% + 1 Ω)
5 Ω
± (6.0% + 5 Ω)
10 Ω
± (10% + 10 Ω)
50 Ω
Approx. 25%
1 mA
± (2.5% + 2 mA)
0.001 A
± (2.5% + 2 mA)
0.01 A
± (2.5% + 20 mA)
7

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

3730

Table of Contents