3.4
Turn the function switch to desired test voltage range (250V, 500V or
1000V).
Connect the black test lead to the (COM) terminal and the red one to
the (VΩ) terminal.
Connect the test lead to sample under test.
Warning: Do not activate the test before the leads are properly connected
to the sample under test.
Do not remove the test leads from the sample under test before the
discharge process is completed.
Press the TEST button and hold it down until the measurement is
stabilized. The display is automatically locked (automatic HOLD).
The
voltage output.
The measured resistance value is displayed on the screen. The HOLD
symbol is lit.
Megohmmeter Model 6527
0.561.8187
Measuring MΩ Insulation Resistance
symbol lights during the measurement indicating active