Installation Guide
DEVIreg™ 532
Electronic Thermostat
www.DEVI.com

Advertisement

loading

Summary of Contents for DEVI 532

  • Page 1 Installation Guide DEVIreg™ 532 Electronic Thermostat www.DEVI.com...
  • Page 3: Table Of Contents

    ..Introduction DEVIreg™ 532 is an electronic thermostat provided with a 2- pole switch, a room sensor to control the room tempera- ture, and an additional floor sensor to limit the maximum floor temperature.
  • Page 4: Technical Specifications

    DEVIreg™ 532 Technical Specifications Operation voltage 220-240V~, 50Hz Standby power consump- Max 0.25W tion Relay: Resistive load Max 15A / 3450W @ 230V Inductive load cos φ= 0.3 max 1A Sensing units NTC 15kOhm at 25°C Sensing values: 0°C 42 kOhm 25°C...
  • Page 5: Safety Instructions

    DEVIreg™ 532 Type Storage temperature -20 to +65°C IP class Protection class Class II - Dimensions 85 x 85 x 36mm Weight The product complies with the EN/IEC Standard "Automatic electrical controls for household and similar use": ▪ EN/IEC 60730-1 (general) ▪...
  • Page 6: Mounting Instructions

    DEVIreg™ 532 Please also note the following: ▪ The installation of the thermostat must be done by an authorized and qualified installer according to local regulations. ▪ The thermostat must be connected to a power supply via an all-pole disconnection switch.
  • Page 7 DEVIreg™ 532 Do not place the thermostat on the inner side of an exterior wall. Always install the thermostat at least 50 cm. from windows and doors. Do not place the thermostat in a way that it will be exposed to direct sunlight.
  • Page 8 DEVIreg™ 532 ▪ Place the floor sensor in a conduit in an appropriate place where it is not exposed to sunlight or draft from door openings. ▪ Equally distant and >2cm from two heating cables. ▪ The conduit should be flush with the floor surface - countersink the conduit if necessary.
  • Page 9 DEVIreg™ 532 2. Connect the thermostat according to the connection diagram. LOAD LOAD Mains Max. Load 220-240V~ 15 (1) A IP31 -10T30 D532 The screen of the heating cable must be connected to the earth conductor of the power supply cable by us- ing a separate connector.
  • Page 10: Settings

    DEVIreg™ 532 Settings How to change the minimum and maximum floor tem- peratures 1. Remove the adjust- ment button. 2. Move the pins to the desired positions. 3. Put the adjustment button back in place. Note Please be aware of the following: ▪...
  • Page 11: Warranty

    DEVIreg™ 532 Thermal Examples of floor- Details Approximate resist- setting for ance 25˚C floor [m2K/W] temperature 0.05 8 mm HDF based 28˚C > 800 kg/m laminate 0.10 14 mm beech par- 650 - 800 31˚C quet kg/m 0.13 22 mm solid oak 32˚C...
  • Page 12: Disposal Instruction

    DEVIreg™ 532 Disposal Instruction Installation Guide...
  • Page 13 DEVIreg™ 532 Installation Guide...
  • Page 14 DEVIreg™ 532 Installation Guide...
  • Page 15 This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed. All trademarks in this material are property of the respective companies. DEVI and the DEVI logo- type are trademarks of Danfoss A/S.