7) Quick Facts and FAQ:
Question:
How does the SP2 and SP8 record the sensor data and how much can it store?
Answer:
The sensorProbe2 will record and store the changes for the dry contacts and sensors as the units
hardware has a data logger where it stores this data in memory. It can save 8,640 points per
sensor. So, if you set your collection time period for 15 minutes for example, then you can save
data up to 3 months on the unit.
Question:
Can you please tell how often the sensorProbe unit interrogates each sensor to obtain the
sensor's readings?
Answer:
This really depends on the sensor type that you have connected to the unit. The switch type
sensor interrogates with the sensorProbes more than 2 times per second.
The temperature and analog type sensors interrogate 1 time per second.
But all of the readings depend on the environment like the number of sensors you have online
and your email and SNMP trap alert settings.
Question:
Is there a way to reboot the sensorProbe unit's web interface remotely?
Answer:
Yes, you can reboot the unit's web interface remotely using this SNMP command and OID here:
snmpset -m all -v 1 -c <community> <IPaddress> .1.3.6.1.4.1.3854.1.2.2.1.106.0 i 1
Question:
Is there any way to edit the content of the email alerts that are sent out from my sensorProbe
unit?
Answer:
Yes, we have have added a separate e-mail notification function. You can set this by using the
following SNMP command:
snmpset -m all -v 1 -c <community> <ip address> .1.3.6.1.4.1.3854.1.2.2.1.112.0 I <separate>
When <community> is admin password <ip address> is ip address of the unit
<separate> is for the separate e-mails or not if this value is 1 it will have the separate e-mails
if this value is 0 it will not have the separate e-mails.
Question:
I have forgotten the IP address that my sensorProbe is configured with. Is there a way I can
determine this IP?
Answer:
Updated until firmware 413