Performance Data - IDEAL IMAX XTRA E320 Installation And Servicing

Hide thumbs Also See for IMAX XTRA E320:
Table of Contents

Advertisement

Table 1 Performance Data
Boiler
Boiler output
Max
(non-condensing)
Mean 70
C
Min
o
Boiler output
Max
(condensing)
Mean 40
C
Min
o
Boiler Input
Net
Max Rate
Gross
Boiler Input
Net
Min Rate
Gross
Maximum Gas Rate
Approx. flue gas
@ max. rate
volume (@80
C) i.e. non-condensing ft
o
Max. Flue Resistance
Flue Gas CO
@ Max Rate
2
G20/LNG
@ Min. Rate
NOx with O
= 0%
2
Seasonal Boiler Efficiency (Building Regs L2)
Table 2 General Data
Boiler
Gas supply
Gas supply connection
Flow connection
*
Return connection
*
Hydraulic Resistance @ 20
(with optional water header pack fitted)
Max Press (sealed system)
Maximum Static Head
Boiler Electricity Supply
Boiler Fuse Rating
Power Consumption (boiler only)
Air Inlet
Flue Size dia
Condensate drain
Boiler dry weight
(unpacked exc. headers)
Water Content
Electricity supply and Fuse rating for pumps etc. refer to manufacturer's instructions.
* OPTIONAL HEADER PACK HAS DN80 CONNECTIONS FOR FLOW AND RETURN AND 2" BSP GAS CONNECTION
Note.
Natural gas consumption is calculated using a calorific value of
37.8MJ/m
(1038Btu/ft
) gross or 34 MJ/m
3
3
and 1013.25 mbar.
a. For l/s divide the gross heat input (kW) by the gross C.V. of the gas
(MJ/m
)
3
b. For ft/h
divide the gross heat input (Btu/h) by the gross C.V. of the
3
gas (Btu/ft
).
3
HEALTH & SAFETY DOCUMENT NO. 635
The electricity at work regulations, 1989. The manufacturer's notes
must NOT be taken, in any way, as overriding statutory obligations.
CAUTION.
To avoid the possibility of injury during the installation, servicing or cleaning of this
appliance, care should be taken when handling edges of sheet steel components.
2
E320
kW
314.6
Btu/h
1,074,178
kW
67.8
Btu/h
231,300
kW
329.0
Btu/h
1,122,500
kW
75.3
Btu/h
256,900
kW
320
Btu/h
1,091,800
kW
355.4
Btu/h
1,212,600
kW
70
Btu/h
238,800
kW
77.6
Btu/h
264,800
m
/h
32.2
3
ft
/h
1138
3
m
/h
484
3
/h
17,100
3
Pa
145
%
9.3/9.8
%
9.1/9.6
mg/kWh
35
ppm
20
95.7
E320
(in. BSP)
2 x R1
(in. BSP)
2 x R2
(in. BSP)
2 x R2
C
mbar
100
o
bar (psi)
6 (87)
m (ft)
61 (200)
W
800
O/D mm
110x2
mm
200
mm
2x21.5
kg (lb)
336 (740)
l (gal)
35 (7.8)
(910 Btu/ft
) nett at 15
3
3
GENERAL
E400
393.2
1,342,552
97.7
333,400
415.6
1,418,000
107.5
366,800
400
1,364,800
444.2
1,515,600
100
341,200
110.9
378,400
40.2
1420
604
21,380
145
9.3/9.8
9.1/9.6
26
15
95.7
E400
2H - G20 - 20mbar
2 x R1
2 x R2
2 x R2
105
6 (87)
61 (200)
2 x External 5A supplies
800
110x2
250
2x21.5
396 (874)
36.8 (8.2)
IMPORTANT. These appliances are CE certified for safety
and performance. It is, therefore, important that no external
control devices, e.g. flue dampers, economisers etc., are
C
o
directly connected to these appliances unless covered by
these Installation and Servicing Instructions or as otherwise
recommended by Ideal Boilers in writing. If in doubt please
enquire.
Any direct connection of a control device not approved by
Ideal Boilers could invalidate the certification and the normal
appliance warranty. It could also infringe the Gas Safety
Regulations and the above regulations.
E480
471.8
1,610,926
105.5
360,000
498.8
1,701,900
116.1
396,100
480
1,637,800
533.0
1,818,600
108
368,500
119.8
408,800
48.4
1710
726
25,640
145
9.3/9.8
9.1/9.6
26
15
95.7
E480
2 x R1
2 x R2
2 x R2
110
6 (87)
61 (200)
230V - 50Hz
Internal 2AT.4AT (x2)
800
110x2
250
2x21.5
430 (948)
48.0 (10.6)
IMAX XTRA -
Installation & Servicing
E560
550.5
1,879,642
107.7
367,500
581.8
1,985,100
118.3
403,600
560
1,910,700
621.8
2,121,600
110
375,300
122.0
416,300
56.4
1992
846
29,920
145
9.3/9.8
9.1/9.6
26
15
95.7
E560
2 x R1
2 x R2
2 x R2
120
6 (87)
61 (200)
800
110x2
250
2x21.5
466 (1028)
54.4 (12.0)