34 STANDARD CONTROLS ACCESS CONT'D
Info mode cont'd.........
Press
Display
N. 0 0
I .
0 0
I.
0 0
Service Mode
L 6 0
or
It is possible for servicing purposes to run the boiler on maximum or minimum loads.
This mode is entered from normal operating mode.
Press
Display
X X X X
S t b y
several times
0
2 8
Wait a few
seconds
Press the 'mode' and '-' button simultaneously for 3 seconds.
Press
OR
Press the 'mode' and '+' button simultaneously for 3 seconds.
Press
*
Last 3 digits are actual flow temperature
This mode will end automatically after 15 minutes. Alternatively to escape sooner press the '+' and '-' simultaneously.
In order to set the Module to a fixed fan speed proceed to CODE MODE (Page 32) and select 'PARA' mode 47 (Page 28).
IMAX XTRA -
Installation & Servicing
INSTALLATION
Description
Burner Run Hours, DHW
100 thousands/10 thousands
Burner Run Hours, DHW
thousands/hundreds
Burner Run Hours, DHW
tens/units
H 8 0
Description
As found
Standby display
Normal Display
Display
Description
*
L
6 0
'Min. Load'. Run for 15 mins
Display
Description
*
H 8 0
'Max. Load'. Run for 15 mins
31