Data Mode - IDEAL imax plus F80 Installation And Servicing

Table of Contents

Advertisement

30 DATA MODE

By pressing the mode key twice, DATA mode is displayed. In this mode it is possible to read information on the operation of the boiler.
Press
Display
D A T A
Twice
Data Accessible to Installer and User. Data relevant to the whole boiler.
Press
Display
T O T
1 . X X
2 . X X
3 . X X
4 . X X
5 . X X
6 . X X
X X X X
8 . X X
Data Accessible only to the Installer by previously entering the service code. Data relevant to individual burners.
Press
Display
B U R 1
B U R 2
B U R 3
B U R 4
B U R 5
-
Installation & Servicing
INSTALLATION
Description
Global flow temperature
Global return temperature
DHW temperature
Outside temperature
N/A
Flow temperature set point
Fan speed set point
Output calculated in % (100% per module)
Press
Display
Description
1 . X X
Local flow temperature, NTC1
2 . X X
Local return temperature, NTC2
X X X X
Module 1 fan speed setpoint
X X X X
Module 1 actual fan speed
Local flow temperature, NTC1
1 . X X
2 . X X
Local return temperature, NTC2
X X X X
Module 2 fan speed set point
X X X X
Module 2 actual fan speed
Local flow temperature, NTC1
1 . X X
2 . X X
Local return temperature, NTC2
X X X X
Module 3 fan speed set point
X X X X
Module 3 actual fan speed
Local flow temperature, NTC1
1 . X X
Local return temperature, NTC2
2 . X X
X X X X
Module 4 fan speed set point
X X X X
Module 4 actual fan speed
Local flow temperature, NTC1
1 . X X
2 . X X
Local return temperature, NTC2
X X X X
Module 5 fan speed set point
X X X X
Module 5 actual fan speed
Unit
ºC
ºC
ºC
ºC
ºC
ºC
rpm
%
Unit
ºC
ºC
rpm
rpm
ºC
ºC
rpm
rpm
ºC
ºC
rpm
rpm
ºC
ºC
rpm
rpm
ºC
ºC
rpm
rpm
27