MASTER AND SLAVE BOILER CONTROL MODULE ERROR CODES CONTINUED
Code
Description
29
Incorrect tacho signal from fan
30
Flow/return temperature differential too high
31
Flow thermistor short circuit
32
Return thermistor short circuit
33
Tank sensor short circuit
35
Flue thermistor short circuit
36
Flow thermistor open circuit
37
Return thermistor open circuit
38
Tank sensor open circuit
40
Flue thermistor open circuit
44
Internal Failure
52
Flue gas temperature too high
60
Error reading parameters
61
Air pressure switch closed when it should be open
107
Heat exchanger thermistor short circuit
108
Heat exchanger thermistor open circuit
109
Heat exchanger temperature too high
110
Heat exchanger temperature too low
111
Heat exchanger to return temperature differential too high
112
Heat exchanger temperature rise too fast
113
No valid mains frequency detected
114
Invalid or conflicting cascade address
115
Internal error
IMAX XTRA -
Installation & Servicing
FAULT FINDING
Action
Check wiring to fan. If wiring OK replace fan.
Check no air in system or boiler
Check adequate flow of water through boiler
Check wiring
Disconnect terminals from thermistor & confirm short
circuit using meter
Replace thermistor
Check wiring
Disconnect terminals from thermistor & confirm short
circuit using meter
Replace thermistor
Not fitted check parameter 46 settings
Check wiring
Disconnect terminals from thermistor & confirm short
circuit using meter
Replace thermistor
Check wiring
Disconnect terminals from thermistor & confirm open
circuit using meter
Replace thermistor
Check wiring
Disconnect terminals from thermistor & confirm open
circuit using meter
Replace thermistor
Not fitted check parameter 46 settings
Check wiring
Disconnect terminals from thermistor & confirm open
circuit using meter
Replace thermistor
Check wiring harness & connections
If wiring OK replace control module
Check no air in system or boiler
Check adequate flow of water through boiler
Press reset. If fault keeps re-occuring replace control module.
Check for blockages in air pressure switch sensing pipes
Check air pressure switch and replace if necessary
Check wiring
Disconnect terminals from thermistor & confirm short
circuit using meter
Check wiring
Disconnect terminals from thermistor & confirm open
circuit using meter
Replace thermistor
Check no air in system or boiler
Check adequate flow of water through boiler
Check no air in system or boiler
Check adequate flow of water through boiler
Check no air in system or boiler
Check adequate flow of water through boiler
Check no air in system or boiler
Check adequate flow of water through boiler
Check power supply to boiler
Press reset. If fault keeps re-occuring replace control module.
Check wiring harness & connections
If wiring OK replace control module