Parameter
Description
P0779[0]
Value x2 of analog output scaling [%]
P0780[0]
Value y2 of analog output scaling
P0781[0]
Width of analog output deadband
r0785.0
CO / BO: Status word of analog output
P0809[0...2]
Copy command data set (CDS)
Index:
[0] Copy from CDS
[1] Copy to CDS
[2] Start copy
P0810
BI: command data set bit 0 (Hand / Auto)
P0811
BI: command data set bit 1
P0819[0...2]
Copy inverter data set (DDS)
Index:
[0] Copy from DDS
[1] Copy to DDS
[2] Start copy
P0927
Parameter changeable via specified inter-
faces
r0947[0...63] CO: Last fault code
Displays fault history.
P0970
Factory reset
0
Disabled
1
Parameter reset
21 User Default Parameter Reset
P1000[0...2]
Selection of frequency setpoint
0
No main setpoint
1
MOP setpoint
2
Analog setpoint
3
Fixed frequency
5
USS/MODBUS on RS485
7
Analog setpoint 2
10 No main setpoint + MOP setpoint
11 MOP setpoint + MOP setpoint
12 Analog setpoint + MOP setpoint
13 Fixed frequency + MOP setpoint
15 USS/MODBUS on RS485 + MOP
setpoint
17 Analog setpoint 2 + MOP setpoint
20 No main setpoint + Analog setpoint
21 MOP setpoint + Analog setpoint
22 Analog setpoint + Analog setpoint
23 Fixed frequency + Analog setpoint
25 USS/MODBUS on RS485 + Analog
setpoint
27 Analog setpoint 2 + Analog setpoint
P1001[0...2]
Fixed frequency 1 [Hz]
P1002[0...2]
Fixed frequency 2 [Hz]
P1003[0...2]
Fixed frequency 3 [Hz]
P1004[0...2]
Fixed frequency 4 [Hz]
26
Range
Factory default
-99999 - 99999
100.0
0 - 20
20
0 - 20
0
-
-
0 - 2
[0] 0 [1] 1 [2] 0
0 - 4294967295
0
0 - 4294967295
0
0 - 2
[0] 0 [1] 1 [2] 0
0 - 15
15
-
-
0 - 21
0
0 - 77
1
30
No main setpoint + Fixed frequency
31
MOP setpoint + Fixed frequency
32
Analog setpoint + Fixed frequency
33
Fixed frequency + Fixed frequency
35
USS/MODBUS on RS485 + Fixed fre-
quency
37
Analog setpoint 2 + Fixed frequency
50
No main setpoint + USS/MODBUS on
RS485
51
MOP setpoint + USS/MODBUS on RS485
52
Analog setpoint + USS/MODBUS on
RS485
53
Fixed frequency + USS/MODBUS on
RS485
55
USS/MODBUS on RS485 +
USS/MODBUS on RS485
57
Analog setpoint 2 + USS/MODBUS on
RS485
70
No main setpoint + Analog setpoint 2
71
MOP setpoint + Analog setpoint 2
72
Analog setpoint + Analog setpoint 2
73
Fixed frequency + Analog setpoint 2
75
USS/MODBUS on RS485 + Analog set-
point 2
77
Analog setpoint 2 + Analog setpoint 2
-550.00 - 550.00
10.00
-550.00 - 550.00
15.00
-550.00 -550.00
25.00
-550.00 - 550.00
50.00
Acc.
level
2
2
2
2
2
2
2
2
2
2
1
1
2
2
2
2
SINAMICS V20 Inverter