Branch circuit protection with Type E combination motor controllers (NKJH1/NKJH7)
Frame size
Inverter
power
rating
(kW)
400 V A
0.37
0.55
0.75
1.1
1.5
2.2
B
3.0
4.0
C
5.5
D
7.5
11
15
E
18.5 (HO)
22 (HO)
230 V AA/
0.12
AB/
0.25
A
0.37
0.55
0.75
B
1.1
1.5
C
2.2
3.0
UL/cUL listed (NKJH/NKJH7) Siemens CMCs of the same type with a current rating lower than that is specified in the
1)
table above corresponding to the inverter power rating, and with a voltage rating as well as an interrupting current rating
at least equal to those of the supply circuit may be used.
"." can be 1 or 2; "**" can be 10, 15, 20, 25 or 40; "##" represents the last two digits available in order numbers.
2)
Unventilated enclosure of minimum volume as specified in the table above is required except for 230 V FSAA to FSC
3)
protected by Type E CMCs. There is no minimum enclosure volume requirement for inverters of 230 V FSAA to FSC.
10
CMC model
Maximum
number
rated current
2)
(A)
3RV20.1-1CA**
2.5
3RV20.1-1DA**
3.2
3RV20.1-1EA**
4.0
3RV20.1-1GA**
6.3
3RV20.1-1HA**
8.0
3RV20.1-1JA**
10.0
3RV20.1-1KA**
12.5
3RV20.1-4AA**
16
3RV.03.-4AA##
16
3RV20.1-4AA**
16
3RV2021-4BA**
20
3RV.03.-4BA##
20
3RV20.1-4AA**
16
3RV2021-4DA**
25
3RV.03.-4DA##
25
3RV.03.-4HA##
50
3RV104.-4HA##
50
3RV2021-4EA**
32
3RV.03.-4HA##
50
3RV104.-4JA##
63
3RV104.-4KA##
75
3RV104.-4LA##
90
3RV20.1-1DA**
3.2
3RV20.1-1FA**
5.0
3RV20.1-1HA**
8.0
3RV20.1-1JA**
10.0
3RV20.1-1KA**
12.5
3RV20.1-4AA**
16
3RV2021-4BA**
20
3RV.03.-4BA##
20
3RV20.1-4AA**
16
3RV2021-4CA**
22
3RV.03.-4BA##
20
3RV20.1-4AA**
16
3RV2021-4EA**
32
3RV.03.-4EA##
32
3RV2021-4EA**
32
3RV.03.-4FA##
40
3RV104.-4FA##
40
1)
Maximum rated
SCCR of SINAMICS
power at 3-ph
V20 with CMC
460 V/1-ph 230 V
(hp)
1
65 kA, 480Y/277 VAC
1.5
2
3
5
5
7.5
65 kA, 480Y/277 VAC
10
10
10
65 kA, 480Y/277 VAC
10
15
10
65 kA, 480Y/277 VAC
15
20
40
65 kA, 480Y/277 VAC
40
20
50 kA, 480Y/277 VAC
40
65 kA, 480Y/277 VAC
50
60
65 kA, 480Y/277 VAC
75
0.25
65 kA, 240 VAC
0.5
1
1.5
2
2
65 kA, 240 VAC
3
3
2
3
3
2
65 kA, 240 VAC
5
50 kA, 240 VAC
5
65 kA, 240 VAC
5
50 kA, 240 VAC
7.5
65 kA, 240 VAC
7.5
Minimum en-
closure volume
(m
/cu. in.)
3
3)
0.007/427
0.012/732
0.019/1159
0.23/14035
0.37/22578
-
-
-
SINAMICS V20 Inverter
A5E37281078-003, 05/2016