Midea R22 T1 side-discharge duct manual
10) Query for Initialization Function Parameters
After setting the initialization function, use the following method for query:
※ Long press FAN SPEED for 2 seconds to enter into the query interface.
※ After enter to the interface, the LCD temperature display area, minute display area will
display a series of numbers, which is the current initialization parameter value. If the current
initialization function is cooling and heating (00), no power-off memory (21), the filter screen
cleaning time is 5000 hours (33), centigrade display (60), their combination is 0130, and it
will display 0130.
※ After enter to the interface for 3 seconds, it will automatically exit.
※ Under this interface, it will not respond any key operation.
11) Indoor unit address setting and query
※ Long press the LOCK key for 5 seconds, enter into the indoor unit address setting interface.
※ After enter into the interface, the temperature display area will display 00, means the address
which is going to be set, then press TEMP ▲ and TEMP ▼ to select the address, and then
press the FAN SPEED key to finish indoor unit address setting.
※ After enter into the interface, press MODE key to query the address.
※ Under the address setting interface, long press LOCK for 5 seconds again, then it will quit the
indoor unit setting interface.
9.5 Wired controller installation
Accessory of wired controller
Accessory name
Wired controller
Wood mounting screw
Mounting screw
Installation manual
Owner's manual
74
Quantity
1
3
M4×20, for mounting on the wall.
3
M4×25, for mounting on the electrical switch box.
1
1
MCAC-RTSM-201301-01
Remarks
With cover.
\
\