Midea R22 T1 side-discharge duct manual
Use a vacuum pump to expel the air.
Loosen and remove the maintenance orifice nut of valve A, and connect the filter hose of
the manifold valve to the maintenance orifice of valve A. (Tighten both valve A
B.)
Connect the filter hose adapter to the vacuum pump.
Open the low pressure (Lo) handle of the manifold valve completely.
Start the vacuum pump to extract air. At the beginning of extracting air, slightly loosen the
maintenance orifice nut of valve B.
Check whether any air enters it (the vacuum pump noise changes, and the multimeter
indicaters from negative to 0). Then tighten this maintenance orifice nut.
Upon completion of vacuuming, tighten the low pressure (Lo) handle of the manifold valve
completely and stop the vacuum pump.
Keep extracting air for over 15 minutes, and check whether the multimeter points at
-1.0×10Pa(-76cmHg).
Loosen and remove the square-head cover of valves A and B. After opening valves A and B
completely, tighten the square-head cover of valves A and B.
Remove the filler hose off the maintenance orifice of valve A, and then tighten the nut.

3.6 Refrigerant replenishment quantity

If the connecting pipe length of indoor unit and outdoor unit is more than 10 meters, then it needs to
replenish refrigerant into the system for the unit normal operation.
The refrigerant for replenishment is R22.
The calculation for the replenished quantity of refrigerant is as the following formula:
Q =Qs× Lt
Q: The replenishing amount of refrigerant; Unit: kg.
Qs: Corresponding unit length of replenishing amount with different liquid pipe diameters; Unit: kg/m.
Diameter of liquid-side pipe
Lt: Total length of extend liquid pipe, it is also means to the total length of liquid pipe; unit: m.
24
Ф9.52mm
Quantity of refrigerant replenished
0.065kg/m
MCAC-RTSM-201301-01
and valve