MCAC-RTSM-201301-01
Expel air by refrigerant
Use the refrigerant in the outdoor unit to expel air.
Screw up the pipe nuts at A, B, C and D completely.
Loosen and remove the square-head cover of valves A and B, and rotate the square-head
spool of valve B counterclockwise for 45 degrees.
Stay for about 10 seconds, and then close the spool of valve B tightly.
Detect leak for all adapters at A, B, C and D. After making sure that no leak exists, open the
maintenance orifice nut of valve A.
After all air is expelled, tighten the maintenance orifice nut of valve A.
Open the spools of valves A and B completely.
Tighten the square-head cover of valves A and B completely.
Use refrigerant tank to expel air.
Screw up the pipe nuts at A, B, C and D completely.
Loosen and remove the square-head cover and the maintenance orifice nut of valves A and
B.
Connect the filler hose of the refrigerant tank with the maintenance orifice of valve A.
Loosen the valve of the refrigerant tank, continue filling refrigerant for 6 seconds to expel the
air, and tighten the nut of valve B quickly.
Loose the valve of the refrigerant tank again, and fill the refrigerant for 6 seconds. Detect
leak for all adapters at A, B, C and D.
After making sure that no leak exists, screw off the filler hose, and after all the filled
refrigerant is expelled, screw up the maintenance orifice nut of valve A quickly.
Open the square-head spools of valves A and B completely.
Tighten the square-head cover of valves A and B.