Electric Connection - Midea MTA1-76HR Technical Manual

Table of Contents

Advertisement

MCAC-RTSM-201301-01
bushes to preserve heat of the drain pipe. Ohterwise, condensate will occur.

3.9 Electric connection

Use special power supply for the air conditioner. Design power supplies specific to the indoor
unit and outdoor unit. The supply voltage must comply with the nominal voltage.
The external supply circuit of the air conditioner must have a ground wire, and the power supply
ground wire of the indoor unit must be connected with the external ground wire firmly.
The power wire and the signal wire shall be laid out neatly and properly, without mutual
interference or contacting the connection pipe or valve.
No power cable is attached to this equipment. Please select the power cable by reference to the
stipulated power supply specifications. No joint of wires is allowed.
Power
Switch capacity of the main
power supply/fuse(A)
Size of power supply wire
Size of power ground wire
Connective wire of indoor &
outdoor unit.
There is a wire of 1m as standard, which is used to connect indoor unit and receiving kit. The
wire also can be customised to maximum lenghth of 3m.
An all-pole disconnection device which has at least 3mm separation distance in all pole and
residual current device(RCD) with the rating of above 10mA shall be incorporated in the fixed
wiring according to the national rule.
The appliance should be installed in accordance with national wiring regulations.
Power wires schematic diagram.
Indoor units
220-240V~, 50Hz, 1Ph
15/10
H05RN-F(300/500V)
2
2×2.5mm
H05RN-F(300/500V)
2
2.5mm
Cooling and heating: H07RN-F(300/500V) 4×1.0mm
Cooling only: H07RN-F(300/500V) 2×1.0mm
Midea R22 T1 side-discharge duct manual
Outdoor units
380-415V~, 50Hz, 3Ph
40/32
H07RN-F(450/750V)
2
4×6.0mm
H07RN-F(450/750V)
2
6.0mm
2
2
27