Emerson unidrive sp User Manual page 229

Universal variable speed ac drive for induction and servo motors model sizes 6 to 9
Hide thumbs Also See for unidrive sp:
Table of Contents

Advertisement

Safety
Mechanical
Product
Information
information
Installation
At the same time the ramp will try to increase the frequency back up
to the demand level. If the integral gain is increased too far the first
signs of instability will occur when operating around the point where
field weakening begins. These oscillations can be reduced by
increasing the proportional gain. A system has been included to
prevent regulation because of the opposite actions of the ramps and
the current limit. This can reduce the actual level that the current
limit becomes active by 12.5%. This still allows the current to
increase up to the current limit set by the user. However the current
limit flag (Pr 10.09) could become active up to 12.5% below the
current limit depending on the ramp rate used.
Torque control:
Again the controller will normally operate with an integral term only,
particularly below the point where field weakening begins. The first
signs of instability will appear around base speed, and can be
reduced by increasing the proportional gain. The controller can be
less stable in torque control mode rather than when it is used for
current limiting. This is because load helps to stabilise the controller,
and under torque control the drive may operate with light load.
Under current limit the drive is often under heavy load unless the
current limits are set at a low level.
Line power supply loss and controlled standard ramp:
The DC bus voltage controller becomes active if line power supply
loss detection is enabled and the drive supply is lost or controlled
standard ramp is being used and the machine is regenerating. The
DC bus controller attempts to hold the DC bus voltage at a fixed
level by controlling the flow of current from the drive inverter into its
DC bus capacitors. The output of the DC bus controller is a current
demand which is fed into the current PI controller as shown in the
following diagram.
Current
demand
DC Bus
voltage
controller
DC Bus
capacitor
Although it is not usually necessary the DC bus voltage controller
can be adjusted with Pr 5.31. However, it may often be necessary to
adjust the current controller gains to obtain the required
performance. If the gains are not suitable it is best to set up the drive
in torque control first. Set the gains to a value that does not cause
instability around the point at which field weakening occurs. Then
revert back to open loop speed control in standard ramp mode. To
test the controller the supply should be removed while the motor is
running. It is likely that the gains can be increased further if required
because the DC bus voltage controller has a stabilising effect,
provided that the drive is not required to operate in torque control
mode.
Closed-loop vector and Servo
The Kp and Ki gains are used in the voltage based current controller.
The default values give satisfactory operation with most motors.
However it may be necessary to change the gains to improve the
performance. The proportional gain (Pr 4.13) is the most critical value in
controlling the performance. Either the value can be set by auto-tuning
(see Pr 5.12) or it can be set by the user so that
Pr 4.13 = Kp = (L / T) x (I
fs
Where:
T is the sample time of the current controllers. The drive
compensates for any change of sample time, and so it should be
assumed that the sample time is equivalent to the lowest sample
rate of 167μs.
Unidrive SP Free Standing User Guide
Issue Number: 1
Electrical
Getting
Basic
Installation
Started
parameters
P Pr 4.13
I
Pr 4.14
Frequency
reference
Active current
/ V
) x (256 / 5)
fs
www.controltechniques.com
Running the
SMARTCARD
Optimization
motor
operation
L is the motor inductance. For a servo motor this is half the phase to
phase inductance that is normally specified by the manufacturer. For
an induction motor this is the per phase transient inductance (σL
This is the inductance value stored in Pr 5.24 after the autotune test
is carried out. If σL
the steady state per-phase equivalent circuit of the motor as follows:
σL
L
=
s
s
I
is the peak full scale current feedback = K
fs
Where K
is defined in Table 11-5.
C
V
is the maximum DC Bus voltage.
fs
Therefore:
Pr 4.13 = Kp = (L / 167μs) x (K
= K x L x K
C
Where:
K = [√2 / (0.45 x V
Drive voltage rating
200V
400V
575V
690V
This set-up will give a step response with minimum overshoot after a
step change of current reference. The approximate performance of the
current controllers will be as given below. The proportional gain can be
increased by a factor of 1.5 giving a similar increase in bandwidth,
however, this gives at step response with approximately 12.5%
overshoot.
Switching
frequency
kHz
3
4
6
8
12
16
The integral gain (Pr 4.14) is less critical and should be set so that
Pr 4.14 = Ki = Kp x 256 x T /
Where:
τ
is the motor time constant (L / R).
m
R is the per phase stator resistance of the motor (i.e. half the
resistance measured between two phases).
Therefore
Pr 4.14 = Ki = (K x L x K
= 0.0427 x K x R x K
The above equation gives a conservative value of integral gain. In some
applications where it is necessary for the reference frame used by the
drive to dynamically follow the flux very closely (i.e. high speed closed-
loop induction motor applications) the integral gain may need to have a
significantly higher value.
Technical
Onboard
Advanced
PLC
parameters
Data
cannot be measured it can be calculated from
s
2
L
m
--------- -
L
r
C
x √2 / 0.45 / V
C
x 167μs)] x (256 / 5)
fs
Vfs
415V
2322
830V
1161
990V
973
1190V
809
Current control
Gain
sample time
bandwidth
μs
Hz
167
TBA
125
TBA
83
TBA
125
TBA
83
TBA
125
TBA
τ
m
) x 256 x 167μs x R / L
C
C
UL Listing
Diagnostics
Information
).
s
x √2 / 0.45.
) x (256 / 5)
fs
K
Phase
delay
μs
1160
875
581
625
415
625
229

Advertisement

Table of Contents
loading

Table of Contents