3. SPECIFICATIONS
3.3.4
The AJ65BT-64RD detects wire breakage in the platinum temperature-measuring resistor or cable
used for each channel, and turns on the wire breakage detection flag (RXn4 to RXn7) for the
corresponding channel.
On the AJ65BT-64RD, the wire breakage detection are performed for channels that are enabled for
conversion.
The relationships between the wire breakage detection and conversion enable/disable are shown
below.
No breakage
Breakage
No connection
POINT
• Be sure to set the channels having no platinum temperature-measuring resistor attached to
"conversion disabled."
If a channel having no platinum temperature-measuring resistor attached is set to "conversion
enabled," the wire breakage detection flag will turn on.
• The channels for which wire breakage detection turned on will retain the detected temperature
value immediately prior to the breakage detection, and the conversion completion flag for the
corresponding channel will turn off.
When the detected breakage is fixed, updating of detected temperature value after repair will
be resumed and the conversion completion flag will be turned on again.
• For platinum temperature-measuring resistor wiring details, refer to Section 4.7.

Wire breakage detection

Connection status
Conversion enabled/disabled setting Wire breakage detection flag
Conversion enabled
Conversion disabled
Conversion enabled
Conversion disabled
Conversion enabled
Conversion disabled