3. SPECIFICATIONS
(2) Remote output signal
Device No.
RYn0 to RYn3
RYn4 to RYn7
RY (n+7) 7
RY (n+7) 8
RY (n+7) 9
RY (n+7) A
Signal name
It is possible to designate the conversion enabled or disabled for each channel.
By disabling the conversion at channels not in use, generation of unnecessary wire
breakage detection flags may be prevented and sampling time may be reduced.
ON : Conversion enabled ..... wire breakage detection is conducted at the same time
the temperature of the target object is taken.
OFF : Conversion disabled .... neither temperature taking or wire breakage detection
is conducted.
CH.
By setting of conversion enable/disable, the following changes are made.
conversion
• When conversion is changed from disabled
enable flag
Temperature detection of the enabled channel is commenced.
After the detected temperature value of the corresponding channel is stored in the
remote register, the conversion completion flag of the corresponding channel is
turned on.
• When the conversion is changed from enabled
The conversion completion flag is turned off for the corresponding channel.
For the detected temperature value stored in the remote register, the data
immediately prior to the disable setting will be retained.
It is possible to designate the sampling processing or travel average processing for
each independent channel.
ON : Travel average processing
OFF : Sampling processing
In travel average processing, an average value of four detected temperature value
CH.
samples that were taken during each sampling time is calculated and stored in the
sampling
remote register.
processing/
• When changed from sampling processing
travel average
The conversion completion flag for the corresponding channel is turned off.
processing
An average value of four detected temperature value samples is calculated, and
specification
after it has been stored to the remote register the conversion completion flag of the
flag
corresponding channel is turned on.
• When changed from travel average processing
The conversion completion flag is turned off for the corresponding channel.
After the most recent detected temperature value is stored in the remote register,
the conversion completion flag for the corresponding channel is turned on.
Note : This flag is only valid when the initial data processing completion flag
(RY (n+7) 8) or initial data setting request flag (RY (n+7) 9) is on.
Select whether or not the offset/gain value will be set to "user setting" or "factory
setting."
At the product shipment from factory, the same values for the factory settings are
Offset/gain
stored in the E
value selection
ON : Factory setting (Offset-gain, 100.0
flag
OFF : User setting
Note : This flag is only valid when the initial data processing compensation flag
(RY (n+7) 8) or initial data setting request flag (RY (n+7) 9) is on.
After power on or hardware reset, the initial data are set in the module by turning this
Initial data
flag on during the initial data processing request .
processing
Used when designating sampling processing/travel average processing designation,
completion flag
selecting offset/gain value.
Initial data
Turned on when changing the initial values.
setting request
Used when designating sampling processing/travel average processing, selecting
flag
offset/gain value.
When this flag is turned on, the wire breakage detection flag/write data error flag are
Error reset
reset (turned off), and the error status flags are reset at the same time. However, the
2
request flag
E
PROM error flag may not be reset (turned off) and therefore the error status flag will
remain on.
n : Address assigned to the master module by the station number setting.
3-13
Description
2
PROM for storing the user setting offset/gain values.
Ω
(0 °C equivalent) -300 °C)
MELSEC-A
enabled
disabled.
travel average processing