4. SETTING AND PROCEDURE BEFORE OPERATION
No.
Name
UP/DOWN
Increase/decrease the offset value/gain value of the channel selected by the mode switch.
switch
ON for less than 1.5 seconds : increase/decrease 0.025 °C at a time.
ON for more than 1.5 seconds : increase/decrease 0.1 °C per 0.04 second.
UP
5)
DOWN
Reset switch
Hardware reset
Initialize the remote register of AJ65BT-64RD.
RESET
The initial data processing request flag turns on by turning the switch on.
6)
LED for
operation
status display
RUN
PW
RUN
7)
L RUN
SD
RD
L RUN
L ERR.
L ERR.
8)
Terminal block
Designates the type of platinum temperature-measuring resistor to be connected to AJ65BT-64RD using a short pin as
either Pt100 (JIS, IEC type) or JPt100 (old JIS type).
Platinum
temperature-
measuring
9)
When connecting Pt100
resistor type
designation pin
ON : Power is on
PW
OFF : Power is off
ON :
Normal
Flicker : Read data error occurred
mode
OFF :
Flicker : Flickers when the offset/gain setting switch is set at OFFSET or GAIN
Test mode
OFF :
ON : Normal communication
OFF : Communication disconnected (time over error)
SD
The light comes on during data transmission
RD
The light comes on during data receiving
ON :
Flicker at regular intervals:
Flicker at irregular intervals: Indicates that the terminating resistor is not installed or the module or
OFF:
AJ65BT-64RD3
1
3
5
DA
DG
2
4
DB
SLD
AJ65BT-64RD4
1
3
5
DA
DG
2
4
DB
SLD
Circuit board
Description
Normal operation
24 V DC power failure or WDT error
Flickers at 0.5-second intervals when the offset value or gain value being
used for compensation is within the setting range.
Flickers at 0.1-second intervals when the offset value or gain value being
used for compensation is out of the setting range (out of the temperature
input range or the gain value minus the offset value is smaller than +10°C).
In this case, the offset or gain value cannot be memorized.
Turns off when the offset/gain setting switch is positioned at SET
Communication data error (CRC error)
Station number, baud rate switch setting error
Indicates that the station number or baud rate switch setting was
changed while power was on.
CC-Link dedicated cable is affected by noise.
Normal communication
7
9
11
13
15
17
+24V
24G
A1
b1
SLD
A2
b2
6
8
10
12
14
16
NC
B1
SLD
NC
B2
(FG)
7
9
11
13
15
17
+24V
24G
A1
b1
SLD
A2
b2
6
8
10
12
14
16
(FG)
a1
B1
SLD
a2
B2
When connecting JPt100
4-4
19
21
23
25
27
A3
b3
SLD
A4
b4
18
20
22
24
26
NC
B3
SLD
NC
B4
19
21
23
25
27
A3
b3
SLD
A4
b4
18
20
22
24
26
a3
B3
SLD
a4
B4
(Factory setting is Pt100.)