Mitsubishi AJ65BT-64RD3 User Manual page 65

Pt 100 temperature input module
Hide thumbs Also See for AJ65BT-64RD3:
Table of Contents

Advertisement

6. TROUBLESHOOTING
From the previous page
*1 Check for short-circuits, reversed connection, wire breakage, terminal resistor, FG connection,
overall distance and station-to-station distance.
From the previous page
N
Is "L RUN" LED lit?
Y
Is "SD" LED lit
Is "SD" LED lit
(flickering)?
N
Y
Corresponding
module failure
station number
switch set correctly (not
duplicated with other
Corresponding module failure
(station number switch)
Is the
station number
N
switch set correctly (not
duplicated with other
station)?
Set the station number correctly
Y
Restart the power supply/
Turn ON the reset switch
Corresponding module failure
(station number switch)
N
(flickering)?
Y
Is the baud rate
setting correct?
Y
Are the
communication
cables connected
correctly?
*1
Y
Corresponding module failure
(baud rate switch)
Is the
N
station)?
Set the station number correctly
Y
Restart the power supply/
Turn ON the reset switch
Complete
6-5
MELSEC-A
From the previous page
N
Correct the baud rate setting
Restart the power supply/
Turn ON the reset switch
N
Connect the communication
cables correctly