The following uses have some special functions
which in brief are:
Application 5
"Two-compressor" operation.
The two compressors must be of the same size.
On start-up (after defrosting, operational stop,
etc.) both compressors are started with a set time
shift. One compressor starts at half the differential
so that an optimum adaptation of compressor
capacity takes place for the current load in the
appliance/room. There is automatic runtime
equalisation between the compressors.
For a more detailed description please refer to
earlier sections in the manual.
Hot gas defrosting.
Hot gas defrosting is adapted to commercial
appliances/rooms with limited system filling.
One relay controls the main valve in the suction
line.
A changeover relay controls both the hot gas
valve and the drain valve.
This means that there is no time delay between
stops of hot gas and start of draining.
Application 7
Control of night blinds
Night blinds follow the status of the light function
- when the light is switched on, the night blinds
are up and when the light is switched off, the
night blinds are down. In addition a digital input
provides the option of forced opening of the
blinds so that the appliance can be filled with
products.
Application 8
Heat thermostat
The heat thermostat is typically used if the
temperature is to be controlled within narrower
limits, e.g. for cutting rooms, etc. The heating
thermostat can be set as a difference in relation to
the cutout limit for the refrigeration thermostat so
that simultaneous refrigeration and heating are
avoided.
Two refrigeration sections - two defrost outputs
one valve, two evaporators and two refrigeration
sections.
refrigeration section.
Two refrigeration sections - one defrosting
output.

This application is for refrigeration appliances with

one valve, one evaporator and two refrigeration
sections.

Alarm monitoring and display readings take

place individually via the "S3" sensors in each
refrigeration section. Separate product sensor can
be connected.
AK-CC 550B
5
6
7
8
9
10
Manual RS8GL302 © Danfoss 2016-03