Auxiliary schedule for settings (quick-setup)
Preset settings (o62)
Temperature (SP)
Max. temp. setting (r02)
Min. temp. setting (r03)
Sensor signal for thermostat. S4% (r15)
Alarm limit high (A13)
Alarm limit low (A14)
Sensor signal for alarm funct.S4% (A36)
Interval between defrost (d03)
Defrost sensor: 0=time, 1=S5, 2=S4 (d10)
DI1 config. (o02)
Sensor signal for display view S4% (017)
AK-CC 550B
Defrost stop on
time
1
2°C
6°C
0°C
8°C
-5°C
0%
6 h
0
Case cleaning (=10)
Manual RS8GL302 © Danfoss 2016-03
Case
Defrost stop
Defrost stop on
on S5
2
3
-2°C
-28°C
4°C
-22°C
-4°C
-30°C
100%
6°C
-15°C
-5°C
-30°C
100%
6h
12h
1
1
0%
Room
Defrost stop
time
on S5
4
5
4°C
0°C
8°C
5°C
0°C
-2°C
0%
10°C
8°C
0°C
0°C
0%
8h
8h
0
1
Door function (=2)
6
-22°C
-20°C
-24°C
-15°C
-30°C
6h
1
27