6.1 Possible Failures at Preparation of the CF
This section describes the causes and remedies of the possible failures
that are assumed to occur during setup.
Possible Failures at Preparation of the CF
These failures may occur during the following operations.
Section 2.1 "Preparing the CF for YCP21"
Section 3.1 "Preparing the CF/USB for Upgrading"
Failure 1: The selected drives for "mk_vx_cf" tool are not "E:" to "K:".
No.
Cause
1
The USB hub power
supply is not turned ON.
2
The USB hub is not
connected to the USB port
of the personal computer.
3
The USB hub is not
connected to the CF
reader/writer.
4
The CD drive is not set to
an appropriate drive (K).
6-1
The "E:" drive is
not displayed.
"Not Use" is
displayed.
Remedy
Connect the AC adapter to the USB hub
and insert the AC adapter into the 100-V
power supply.
Connect the USB hub to the USB port of
the personal computer.
Connect the USB hub to the CF reader/
writer.
Take above remedies 1 to 3, and then
restart the personal computer.
HW1481993