TABLE 4: Electrical Heat: Minimum Fan Speed
Heater Kit
Nom. kW
1,2,3
@240V
Models
6HK(0,1)6500206
2.4kW
6HK(0,1)6500506
4.8kW
6HK(0,1)6500806
7.7kW
6HK(0,1)6501006
9.6kW
6HK36501025
6HK(1,2)6501306
12.5kW
6HK(1,2)6501506
14.4kW
6HK36501525
6HK(1,2)6501806
17.3kW
6HK36501825
6HK(1,2)6502006
19.2kW
6HK46502025
6HK(1,2)6502506
24kW
6HK46502525
1. (0,1) - 0 = no service disconnect OR 1 = with service disconnect.
2. (1,2) - 1 = with service disconnect, no breaker jumper bar OR 2 = with service disconnect & breaker jumper bar.
3. 6HK3 = 3-Phase with terminal block connectors only, 6HK4 = 3-Phase with service disconnect.
TABLE 5: KW & MBH Conversions - For Total Power Input Requirement
For a power distribution voltage that is different than the provided nominal voltage, multiply the kW and MBH data from the table by the conversion
factor in the following table.
DISTRIBUTION POWER
208V
220V
230V
TABLE 6: Electric Heat Performance Data: 208/230-1-60 & 208/230-3-60
Heater
1,2,3
Models
6HK(0,1)6500206
6HK(0,1)6500506
6HK(0,1)6500806
6HK(0,1)6501006
1PH
6HK(1,2)6501306
6HK(1,2)6501506
6HK(1,2)6501806
6HK(1,2)6502006
6HK(1,2)6502506
6HK36501025
6HK36501525
3PH
6HK36501825
6HK46502025
6HK46502525
1. (0,1) - 0 = no service disconnect OR 1 = with service disconnect.
2. (1,2) - 1 = with service disconnect, no breaker jumper bar OR 2 = with service disconnect & breaker jumper bar.
3. 6HK3 = 3-Phase with terminal block connectors only, 6HK4 = 3-Phase with service disconnect.
4. For different power distributions, see conversion table on Page 5.
12
18B
24B
30B
Med Lo (#2)Med Lo (#2)Med Lo (#2)Med Lo (#2)Med Lo (#2)Med Lo (#2)Med Lo (#2)Med Lo (#2)Med Lo (#2)Med Lo (#2)
Med Lo (#2) Med (#3)
Med (#3) Med Lo (#2) Med (#3) Med Lo (#2)Med Lo (#2)Med Lo (#2)Med Lo (#2)Med Lo (#2)
Med (#3) Med Hi (#4) Med Hi (#4) Med Lo (#2) Med Hi (#4) Med (#3) Med Lo (#2)Med Lo (#2)Med Lo (#2)Med Lo (#2)
Med (#3) Med Hi (#4) Med Hi (#4) Med Lo (#2) Med Hi (#4) Med (#3) Med Lo (#2)Med Lo (#2)Med Lo (#2)Med Lo (#2)
Med Hi (#4) Med Hi (#4) Med (#3) Med Hi (#4) Med (#3) Med Lo (#2)Med Lo (#2)Med Lo (#2)Med Lo (#2)
Med Hi (#4) Med Hi (#4) Med Hi (#4)
Nominal kW
@240V
208V
2.4
1.8
4.8
3.6
7.7
5.8
9.6
7.2
12.5
9.4
14.4
10.8
17.3
13
19.2
14.4
24
18
9.6
7.2
14.4
10.8
17.3
13
19.2
14.4
24
18
Air Handler Models
36B
36C
Hi (#5)
Med Hi (#4) Med Hi (#4)
Hi (#5)
Med Hi (#4)
Hi (#5)
Hi (#5)
NOMINAL VOLTAGE
240V
240V
240V
4
Total Heat
kW
MBH
230V
208V
230V
2.2
6.2
4.4
12.3
7.1
19.7
8.8
24.6
11.5
32
13.2
36.9
15.9
44.3
17.6
49.2
22
61.5
8.8
24.6
13.2
36.9
15.9
44.3
17.6
49.2
22
61.5
42C
48C
48D
Med (#3)
Med (#3) Med Lo (#2)Med Lo (#2)
Med (#3) Med Hi (#4) Med (#3)
Med Hi (#4)
Hi (#5)
Hi (#5)
CONVERSION FACTOR
0.75
0.84
0.92
kW Staging
W1 Only
208V
230V
7.5
1.8
2.2
15
3.6
4.4
24.1
5.8
7.1
30.1
7.2
8.8
39.2
3.1
3.8
45.1
3.6
4.4
54.2
6.5
7.9
60.2
7.2
8.8
75.2
7.2
8.8
30.1
7.2
8.8
45.1
10.8
13.2
54.2
13
15.9
60.2
7.2
8.8
75.2
9
11
Johnson Controls Unitary Products
60C
60D
Med (#3)
Med Hi (#4) Med Hi (#4)
Med Hi (#4)
W1 + W2
208V
230V
1.8
2.2
3.6
4.4
5.8
7.1
7.2
8.8
9.4
11.5
10.8
13.2
13
15.9
14.4
17.6
18
22
7.2
8.8
10.8
13.2
13
15.9
14.4
17.6
18
22