Maintenance; Air System Adjustment - York AE SERIES Installation Manual

Standard ecm single piece multi-position air handlers
Table of Contents

Advertisement

5169032-UIM-C-0416
TABLE 11: Air Flow Data (CFM)
Models
48C
48D
60C
60D
1. Air handler units have been tested to UL 1995 / CSA 22.2 standards up to 0.50" wc. external static pressure.
Dry coil conditions only, tested without filters.
For optimal performance, external static pressures of 0.2" to 0.5" are recommended. Applications above 0.5" are not recommended.
Airflow data shown is from testing performed at 230V. AE units use a standard ECM constant torque motor, and there is minimal variation of airflow at other distribution
voltage values. The above data can be used for airflow at other distribution voltages.
SECTION XIII: MAINTENANCE
Filters must be cleaned or replaced when they become dirty. Inspect at
least once per month. The frequency of cleaning depends upon the
hours of operation and the local atmospheric conditions. Clean filters
keep unit efficiency high.
COIL CLEANING
If the coil needs to be cleaned, it should be cleaned with water.
LUBRICATION
The bearings of the blower motor are permanently lubricated.
CONDENSATE DRAINS
During the cooling season check the condensate drain lines to be sure
that condensate is flowing from the primary drain but not from the
secondary drain. If condensate ever flows from the secondary drain the
unit should be promptly shut off and the condensate pan and drains
cleaned to insure a free flowing primary drain.
SECTION XIV: AIR SYSTEM ADJUSTMENT
To check the Cubic Feet per Minute (CFM), measure the external duct
static using a manometer and static pressure tips. To prepare coil for
static pressure measurements run the fan only to assure a dry coil.
18
1
Blower
Motor Speed
0.10
#5 HI
1759
#4 MED-HI
1684
#3 MED
1511
#2 MED-LO
1305
#1 LO
1123
#5 HI
1774
#4 MED-HI
1709
#3 MED
1484
#2 MED-LO
1295
#1 LO
1102
#5 HI
1964
#4 MED-HI
1889
#3 MED
1693
#2 MED-LO
1486
#1 LO
1292
#5 HI
1907
#4 MED-HI
1851
#3 MED
1648
#2 MED-LO
1456
#1 LO
1261
External Static Pressure (in. wc.)
0.20
0.30
0.40
1719
1685
1644
1639
1606
1569
1460
1427
1388
1260
1212
1178
1068
1029
985
1726
1684
1651
1668
1619
1580
1436
1410
1372
1254
1218
1167
1051
1011
962
1930
1897
1858
1855
1818
1791
1652
1627
1584
1450
1411
1375
1247
1207
1172
1871
1835
1796
1816
1774
1742
1608
1569
1530
1416
1371
1333
1221
1172
1120
Refer to Table 11 for coil Air Flow Data of Cubic Feet Per Minute
(CFM).
Drill 2 holes, one 12" away from the air handler in the supply air duct
and on 12" away from the air handler in the return air duct (before any
elbows in the duct work). Insert the pressure tips, and energize the
blower motor. See Table 9 to determine the air flow, and make the
necessary adjustments to keep the CFM within the airflow limitations of
the coil.
EXTERNAL DUCT STATIC
Measure the supply air static pressure. Record this positive number.
Measure the return air static pressure. Record this negative number.
Treat the negative number as a positive, and add the two numbers to-
gether to determine the total external system static pressure. If a filter
rack is installed on the return air end of the air handler or indoor coil sec-
tion, make sure to measure the return air duct static between the filter
and the indoor coil.
0.50
0.60
1611
1578
1536
1489
1347
1308
1121
1076
909
793
1614
1574
1548
1499
1321
1284
1114
1069
890
831
1823
1789
1747
1716
1551
1510
1335
1291
1123
1055
1762
1723
1699
1659
1492
1445
1289
1227
1055
998
NOTICE
Johnson Controls Unitary Products
0.70
1540
1452
1262
1027
769
1529
1459
1237
1005
766
1752
1668
1462
1252
990
1681
1616
1404
1163
949