Converters Size A5, A6, A7, C3 And C4 (900; Blown Fuses; Ripple Monitor - ABB DCS 500B Service Manual

Dcs thyristor power converters for dc drive systems 25 to 5200 a
Hide thumbs Also See for DCS 500B:
Table of Contents

Advertisement

Converters size A5,
A6, A7, C3 and C4
(900...5200 A)

Blown fuses

Ripple monitor

DCS 500 / DCS 600 Service Manual
These converters are equipped with fuses in the branches of the
power part.
- The converter must be disconnected from the mains.
- In case of a blown fuse, the faulty thyristor or the faulty pair of
thyristors are already isolated at one side from the others and
therefor the faulty branch is known (see
- The OHM test should be performed, when the thyristor is still
clamped. Outside the converter a special thyristor clamping de-
vice is needed.
- For 4-Q converters with antiparallel thyristors or BCT's:
The selection of a forward or reverse thyristor or BCT (Bidirec-
tional-Controlled-Thyristor) is done during the disassembly. Con-
tinue with related chapter 5, 6, 7, 8, or
- After a thyristor was replaced, the OHM test should be done an-
other time to make sure that all faulty thyristors have been de-
tected! If the motor is still connected to the converter the result of
the measurement may be wrong.
If the ripple monitor fault occured, the fault tracing must be adapted
to the reasons listed before:
- Check the fuses and the thyristors, according to the statements
before.
- If the power section seems to be ok, but still one or more thyris-
tors don´t take current, something went wrong in between the fir-
ing pulse generation and the thyristor´s gate; in this case check:
• Is a firing pulse present on the primary side of the firing pulse
transformer?
• Is a firing pulse present on the secondary side of the firing
pulse transformer?
• Is the firing pulse transfered to the gate of the thyristor? Are
there all electrical connections still healthy?
• Can the thyristor be fired with the applied firing pulse? Is the
pulse form of the firing pulse identical at all measuring posi-
tions?
- Check the settings of the current controller.
- Check the AC mains network by taking recordings of the line
voltage and current at all 3 phases at the same time.
3ADW000093R0701_DCS500B/DCS600_Service manual_e_g
Chapter 2 - Fault Tracing Thyristors
Figure
5-1).
9
Find faulty thyristor
VI A
2 - 3