Firmware Download With Windows Nt 4.0; Recommendation; Preparation - ABB DCS 500B Service Manual

Dcs thyristor power converters for dc drive systems 25 to 5200 a
Hide thumbs Also See for DCS 500B:
Table of Contents

Advertisement

Chapter 10 - Service
Firmware download
with Windows NT 4.0
Recommendation It is strongly recommended:

Preparation

VI A
10 - 18
To use the ABB bus cable (DCA 0021499 R0001).
To disconnect the laptop from mains supply during download.
The drive has to be grounded.
To switch off all other drives beside the destined unit (distur-
bances possible).
to provide save download transmission
Switch off auxiliary supply voltage of SDCS-POW-1.
Disconnect and remove SDCS-AMC x board (only
DCS 600).
Disconnect any other equipment from X33 and X34.
Connect bus cable from NPCU-02 to X33 or X34 at DCS con-
verter.
Connect the interface NPCU-02 to COM1 at the PC.
Set Jumper S2 on SDCS-CON-x from position 7-8 or 3-4 to 5-6.
Copy the files distributed from ABB
into designated pathes e.g.
C:\...\DCSx00
Start HyperTerminal by double-click on CON2 download.ht.
This setup file configures HyperTerminal to communicate with the
SDCS-CON-x board.
3ADW000093R0701_DCS500B/DCS600_Service manual_e_g
(see Software
DCS 500 / DCS 600 Service Manual
configuration)