Partition-Specific Fields

(Duplicate this page for each partition in the installation.)
To program these fields,
1. Press *91 to select a partition.
2. Enter a partition-specific field number (ex. *09).
3. Make the required entry.
4. Repeat steps 1-3 for the other partition in the system.
1st Page Fields
*09
ENTRY DELAY #1
00, 02-15 times 15 seconds.
Maximum 03 for UL Listed installations.
*10
EXIT DELAY #1
00, 03-15 times 15 seconds.
Maximum 04 for UL Listed installations.
*11
ENTRY DELAY #2
00, 02-15 times 15 seconds.
Maximum 03 for UL installations.
*12
EXIT DELAY #2
00, 03-15 times 15 seconds.
Maximum 04 for UL installations.
*13
ALARM SOUNDER DURATION
01-15 times 2 minutes.
Must be minimum 16 minutes for UL installations.
*16
CONFIRMATION OF ARMING DING
1=enable; 0=disable.
Must be "1" for UL installations.
*22
KEYPAD PANIC ENABLES
1=enable; 0=disable
*23
MULTIPLE ALARMS
1=yes; 0=no. Must be 1 for UL installations.
*29
QUICK ARM
1=yes; 0=no
*32
PRIM. SUBS. ACCT #
Enter 00-09; B-F (11-15) [15 15 15 15]
*38
PREVENT ZONE XX BYPASS
001-64; 000 if all zones can be bypassed
*39
ENABLE OPEN/CLOSE REPORT
FOR INSTALLER CODE
1=enable; 0=disable
*84
SWINGER SUPPRESSION
01-15 alarms; Must be "00" (disabled) for UL installations.
*85
ENABLE DIALER REPORTS FOR PANICS & DURESS
1=enable; [0=disable]
*87
ENTRY WARNING
1=continuous; 0=3 beeps
PARTITION #____ PROGRAM FIELDS
|
[02]
|
[04]
|
[06]
|
[08]
|
[04]
[0]
[001]
995 996 999
[1]
[1]
|
|
|
|
|
[00]
[1]
|
[03]
995 996 999 Duress
[1]
*88
BURG. ALARM COMM. DELAY
1=16 seconds; 0=no delay. Must be "0" for UL installations.
*90
SEC. SUBS. ACCT #
Enter 00-09; B-F (11-15)
2nd Page Fields
1*43
PERM. KEYPAD BACKLIGHT
1=enable; 0=disable When disabled, display lights when
any key is pressed, and turns off after period of keypad
inactivity.
1*45
EXIT DELAY SOUNDING
1=enable; 0=disable. Produces quick beeping during exit
delay if enabled.
1*47
CHIME ON BELL 1
1=enable; 0=disable
1*52
SEND CANCEL IF ALARM + OFF
1=no restriction; 0=within Bell Timeout period only
1*76
ACCESS CONTROL RELAY FOR PART.[00]
Relay will be pulsed for 2 seconds whenever code + [0] is
pressed. Enter 00-08; 00=none. Must be "00" for UL installs.
3rd Page Fields
2*18
ENABLE GOTO FOR THIS PARTITION
1=Allow log-on from other partitions; 0=disable
2*20
ENABLE J7 TRIGGERS BY PARTITION
0=disable; 1=enable for
SUMMARY OF PROGRAMMING COMMANDS
To enter program mode, enter installer code + [8] + [0] +
[0]
To set standard defaults, press *97
To change to next page of program fields, press *94
To return to previous set of fields, press *99
To erase account and phone number field entries,
press [*] + field number + [*]
To assign zone descriptors, press #93 + follow menu
prompts
To add custom words, press #93 + follow menu prompts
To enter Installer's Message, press #93 + follow menu
prompts
To exit program mode, enter *99 OR *98: *99 allows re-
access to programming mode by installer code. *98
prevents re-access to programming mode by installer
code.
– 9 –
[0]
|
|
|
[15 15 15 15]
[0]
[0]
[0]
[0]
|
[0]
[1]
|