44 TROUBLESHOOTING
Cause
Lighting instructions not
followed
Plugged main burner orifice
Switching device is defective
Thermopile wires loose at valve
terminals
Thermopile wires ground out
due to pinched wires
Improper refractory panel
placement (if installed)
No LP gas in tank
Incorrect glass frame assembly
installation
Improper pitch on horizontal
venting
Defective thermopile or
thermocouple
Inner vent pipe leaking exhaust
gases back into firebox
Vent cap blockage
Excessive draft
Improper log placement
Improper venturi setting
Incorrect vent cap installation
Vent cap blockage
Improper venturi setting
Incorrect vent cap installation
Blockage or leakage of the vent
system
Solution
Turn gas control knob to ON position.
Turn the ON/OFF rocker switch to ON position.
Put wall switch, remote control, or thermostat in heat demand
position.
Remove blockage as necessary.
Check remote, thermostat, or wall switch wires for proper
connection.
Place jumper wires across terminals at switch. If the burner
lights, replace the defective switch, thermostat, or batteries in
remote control as necessary.
If switching device checks out as described above, place
jumper wires across switches on the gas valve. If the burner
lights, the switching wires are faulty or connections are bad.
Replace as necessary.
Tighten if necessary.
Free pinched wires if necessary.
Refractory panels must be tight against firebox walls. It may
be necessary to secure panels with high-temperature sealant,
especially around the intake duct.
Check LP (propane) tank. Refill if necessary.
Refer to Section 8.2 Glass Frame Assembly on page 27.
¼ in (6 mm) per 12 in (30 cm) is required on horizontal venting
Check thermopile and thermocouple for proper millivolts
Check for leaks and repair if necessary.
Remove debris if necessary.
A restrictor may need to be installed or modified. Refer to
Section 11.2.2 Vent Restriction on page 40.
Refer to Section 8.3 #SP34-500 Log Set Installation on page
28.
Venturi may need to be opened slightly to allow more air into the
gas mix. Refer to Section 11.2.1 Burner Venturi on page 39.
Adjust if necessary.
Remove debris if necessary.
Venturi may need to be opened slightly to allow more air into the
gas mix. Refer to Section 11.2.1 Burner Venturi on page 39.
Adjust if necessary.
Check the vent pipe for leaks, and the vent cap for debris.
Repair vent pipe or remove debris from vent cap if necessary.