Position Of The Boiler - DeDietrich GT 330 Technical Instructions

Fuel oil/gas-fired boilers
Hide thumbs Also See for GT 330:
Table of Contents

Advertisement

The dimensions (in mm) correspond to the minimum recommended
dimensions needed to ensure adequate accessibility around the
boiler.
Size A
Standard panel
B
DIEMATIC-m3
Pay attention to the overall volume of the burner when the
door is open. To install several boilers in cascade, these
dimensions should be adapted accordingly.
Warning:
In order to avoid damage to the boilers, it is necessary to prevent the
contamination of combustion air by chlorine and/or fluoride
compounds, which are particularly corrosive.
These compounds are present, for example, in aerosol sprays,
paints, solvents, cleaning products, washing products, detergents,
glues, snow clearing salts, etc.
Therefore:
Do not suck in air evacuated from premises using such
products: hairdressing salons, dry cleaners, industrial premises
(solvents), premises containing refrigeration systems (risk of
refrigerant leakage), etc.
12
Boiler
mm
mm
Panel K3
B3
mm

Position of the boiler

Ventilation: To allow the input of combustive air, sufficient ventilation
must be provided in the boiler room, for which the cross section and
emplacement must satisfy regulations in force in the country in which
the boiler is installed.
GT 334
GT 335
840
1000
105
105
195
195
Do not stock such products close to the boilers.
If the boiler and/or peripheral equipment are corroded by such
chloride or fluoride compounds, the contractual guarantee
cannot be applied.
GT 330
GT 336
GT 337
GT 338
1160
1320
105
105
195
195
10/04/06 - 300007650-001-A
GT 339
1480
1640
105
105
195
195