Boilers For Following Countries: Germany, Poland - DeDietrich GT 330 Technical Instructions

Fuel oil/gas-fired boilers
Hide thumbs Also See for GT 330:
Table of Contents

Advertisement

2.3

Boilers for following countries: Germany, Poland

Conditions of use:
Maximum operating temperature: 100 °C
Maximum operating pressure: 6 bar
Thermostat adjustable from 30 to 90°C
Safety thermostat: 110 °C
Boiler
Useful output
Power input
Number of sections
Number of baffle plates
Water capacity
Maintenance consumption (A)
Water resistance
Flue gas temperature (C)
Pressure in the furnace for nozzle pressure = 0
(B) (C)
Mass flue gas flow rate (C)
DIN 4705 Teil 1
Combustion chamber
Weight (empty)
(A)1 mbar = 10 mmCE = 10 daPa.
(B)Pressure in the furnace for nozzle pressure = 0.
(C)Nominal operation (top boiler power).
10/04/06 - 300007650-001-A
kW
kW
l
∆ T = 30K
%
∆ T = 10K (A+C)
mbar
∆ T = 20K (A+C)
mbar
°C
Pa
(A)
kg per
Fuel oil
sec
kg per
Natural gas
sec
Recorded
mm
diameter
Length
mm
3
Volume
m
kg
Test conditions:
CO² Fuel oil = 13%
CO² Natural gas = 9.5%
Ambient temperature: 20 °C
GT 334
GT 335
GT 336
55-80
80-110
110-140
60-88
88-121
121-154
4
5
6
10
96
116
0.150
0.135
0.125
8.7
16.5
2.1
3.8
< 180
< 180
< 180
20
35
0.037
0.051
0.065
0.039
0.054
0.068
377
377
621
781
0.096
0.122
0.148
612
736
GT 330
GT 337
GT 338
140-175
175-210
154-192
192-231
6
7
8
10
10
12
136
156
176
0.115
0.100
27
41.2
56.9
7
9.6
14.2
< 180
< 180
60
100
150
0.081
0.097
0.085
0.102
377
377
377
941
1101
1261
0.174
0.200
846
981
1103
GT 339
210-250
231-275
9
12
196
0.085
84
20.8
< 180
200
0.115
0.121
377
1369
0.226
1230
9