HART Loop Converter KFD2-HLC-(Ex)1.D(.**)

Display modes and error messages

6
Display modes and error messages
The following appear on the display in normal mode:
the current values for HART variables PV, SV, TV, QV in the selected unit and
the actual current output values Ch1, Ch2, Ch3 in mA.
Please use the
or current output value.
To select the units for the measured values see section 8.2.
The display is updated every time the HLC receives a HART command 3 message from the field
device.
Current output values are displayed as a four-digit number. The decimal point is set to give the best
possible resolution.
The floating decimal values for the HART variables are displayed as follows:
− if possible as a four-digit number with decimal point and without an exponent (negative values
have three digits because of minus sign)
− a number may be rounded up (0.3456 appears as 0.346)
− if this display is not possible, the mantissa and exponent are displayed alternately.
If the restart inhibit (see section 8.5.5 and 8.5.7) is triggered but the device continues operating
normally, a corresponding message appears in the second line of the display.
If a fault occurs, one of the following messages is displayed until the fault is rectified:
Err device fault (red LED lights up)
Err communication error (red LED flashes)
Err sensor fault (red LED flashes)
If switching the HLC on/off and checking the cables does not rectify the fault, please contact
Pepperl+Fuchs or the field device manufacturer.
The relays power down when a fault occurs.
For information on the behaviour of the current output in the event of a fault, see section 8.4.4.