HART Loop Converter KFD2-HLC-(Ex)1.D(.**)
Installation and connection

5.2.1 Connection input (field circuit)

The intrinsically safe field circuit is connected to the blue terminals 1 to 6 on the KFD2-HLC-Ex1.D(.**).
This may be conducted using DIN EN 60079-14-compliant leads into the hazardous area.
You can connect the following three operating modes:
1. any separately powered HART loop with a transmitter or positioner in a parallel circuit (as with
HART handheld terminals, terminals 2 and 3)
2. an active HART-compatible mA source, e. g. a separately powered HART transmitter (terminals 2
and 3, bridge between terminals 5 and 6)
3. a 2-wire HART transmitter (HART transmitter with analogue 4 mA ... 20 mA output signal) powered
by the HLC (terminals 1 and 3, bridge between terminals 4 and 5)
1
2
HART
Zone 0, 1, 2
Div. 1, 2
8
3
+
1+
+
2+
-
-
3-
4
5
6
KFD2-HLC-Ex1.D
ERR
24 V DC
Power Rail
7-
-
+
I
8+
+
-
9-
13+
-
+
II
14-
+
-
15+
19
-
+
III
20
+
-
21
22
23+
24 V DC
24-
Zone 2
Div. 2