Configuration
3.4 Other options when configuring a CP 243-1
Table 3- 4
Structure of the parameter record of a user
Parameter
Access right
User name
Password
Example of a user configuration file
# This is a comment
TIMESTAMP=3D2C4E48
FILETYPE=UDB
FILEFORMAT=01
00|00010048|user_with_all_rights|C~WB1"
01|00000040|Status_CP|UX3MUppLjRzn*R
02|00010000|FTP_access|W9vQ}G cfH
03|00000000||
04|00000000||
05|00000000||
06|00000000||
07|00000000||
78
Description
The access rights are represented in
hexadecimal format.
Bit [0-1] not used
Bit [2] read access to data of the
S7-200 CPU via the HTTP server
0: No
1: Yes
Bit [3] read and write access to data
of the S7-200 CPU via the HTTP
server
0: No
1: Yes
Bit [4-5] not used
Bit [6] access to status page of the
CP 243-1 via HTTP server
0: No
1: Yes
Bit [7-15] not used
Bit [16] access to all FTP functions
0: No
1: Yes
Bit [17-31] not used
The user name is shown in plain text
and consists of 1 to 32 characters
The password is encrypted and stored
with a character length of up to 64
characters (actual password length is
between 1 and 32 characters).
Example
00|00010048|<username>|
<password>
Read and write access via HTTP
Access to status page of the CP
243-1 via HTTP
Access to all FTP functions
00|00000040|Status_CP|<password>
The user with the user name
Status_CP is authorized to read the
status of the CP 243-1
00|00010000|<user_name>|W9vQ}G
cfH
The user with password
!state_Cp1 (encrypted: W9vQ}G cfH) is
authorized to use all FTP functions
Operating Instructions, 03/2012, C79000-G8976-C244-02